INSTALLATION 

The TxBlock transmitter is intended for in head mounting. Its drawing is presented in 
Figure 04. 

 

Figure 04 – TxBlock dimensions 

ELECTRICAL CONNECTIONS 

Figure 4 and 5 below shows the thermocouple wiring. Terminals 1, 2 and 3 are used 
for sensor input. For 2-wire Pt100, terminals 2 and 3 shall be connected together. 
The  LOAD  represents the input shunt of an instrument measuring the 4-20 mA 
current loop. 

 

Figure 05 – Transmitter connections – Pt100 

 

Figure 06 – Transmitter connections – Thermocouple 

Its is important to follow the recommendations below: 

  Signal wires should be installed in grounded in conduits and away from power or 

contactor wires. 

  The instrument should have its own power supply wires, which should not be 

shared with electrical motors, coils, contactors, etc. 

  Installing RC filters is strongly recommended at contactor coils or any other 

inductors. 

  System failure should always be taken into account when designing a control 

panel to avoid irreversible damage to equipment people. 

SPECIFICATIONS 

Sensor input: User defined. The supported sensors are listed in Table 01, along 

with their maximum ranges. 

Thermocouples:  Types J, K, R, S, T, N and E, according to IEC 60584 (ITS-90).  
 

         Impedance >> 1 M

Ω

 

Pt100

 Excitation: 0.17 mA. 2 or 3-wire connection (for 2-wire 
sensors, tie terminals 2 and 3 together). 

α

= 0.00385, 

according to IEC 60751(ITS-90). 

Voltage:      0 to 50 mVdc. Impedance >> 1 M

Ω

 

Sensor Type 

Range 

Minimum Measurement Span 

Thermocouple K 

0 to 1370 °C 

100 °C 

Thermocouple J 

0 to 760 °C 

100 °C 

Thermocouple R 

0 to 1760 °C 

400 °C 

Thermocouple S 

0 to 1760 °C 

400 °C 

Thermocouple T 

0 to 400 °C 

100 °C 

Thermocouple N 

0 to 1300 °C 

100 °C 

Thermocouple E 

0 to 720 °C 

100 °C 

Pt100 

-200 to 650 °C 

40 °C 

Voltage 

0 to 50 mV 

5 mV 

Table 01 – Transmitter input sensors 

Total accuracy: better than 0,3 % of the maximum range for thermocouples and 0,2 
% for Pt100 and voltage; 
Response time: < 100 ms 
Output: 2-wire 4-20 mA, linear with respected to the measured temperature. 
Resolution: 0,004 mA (12 bits). 
Power supply: 12 to 35 Vdc, across the transmitter; 
Maximum load (RL):  RL (max.) = (Vdc – 12) / 0,02 

[

Ω

]

 

   

Were: Vdc= Power supply voltage 

Operating temperature: -40 to 85 °C 
Humidity: 0 to 90 % RH 
Electromagnetic compatibility: EN 50081-2, EN 50082-2 
No isolation between the sensor and the 4-20 mA loop. 
Internal protection against polarity inversion. 
Cold junction compensation for thermocouples. 
Housing: ABS UL94-HB.  
Dimensions: 44 mm (diameter) x 25 mm (height). 