SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Control Logic
Relay Word Bits
57
49A05B
RTD5B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
49T05B
RTD5B trip picked up (SEL-387-5 and SEL-387-6 Relays)
49A06B
RTD6B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
49T06B
RTD6B trip picked up (SEL-387-5 and SEL-387-6 Relays)
49A07B
RTD7B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
49T07B
RTD7B trip picked up (SEL-387-5 and SEL-387-6 Relays)
49A08B
RTD8B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
49T08B
RTD8B trip picked up (SEL-387-5 and SEL-387-6 Relays)
58
49A09B
RTD9B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
49T09B
RTD9B trip picked up (SEL-387-5 and SEL-387-6 Relays)
49A10B
RTD10B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
49T10B
RTD10B trip picked up (SEL-387-5 and SEL-387-6 Relays)
49A11B
RTD11B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
49T11B
RTD11B trip picked up (SEL-387-5 and SEL-387-6 Relays)
49A12B
RTD12B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
49T12B
RTD12B trip picked up (SEL-387-5 and SEL-387-6 Relays)
59
COMFLA
Asserts when communications fails
or when out-of-range temperature data
received from RTDA (SEL-387-5 and SEL-387-6 Relays)
RTDINA
State of external RTDA module’s digital input
(SEL-387-5 and SEL-387-6 Relays)
COMFLB
Asserts when communications fails
or when out-of-range temperature data
received from RTDB (SEL-387-5 and SEL-387-6 Relays)
RTDINB
State of external RTDB module’s digital input
(SEL-387-5 and SEL-387-6 Relays)
ISQTAL
Cumulative through-fault I
2
t on a phase of a
designated winding has exceeded the through-fault I
2
t
threshold ISQT (SEL-387-5 and SEL-387-6 Relays)
Table 4.11
Relay Word Bits Sorted Alphabetically
(Sheet 1 of 13)
Bit
Definition
Row
All
LED targets–not usable in SEL
OGIC
control equations
0
All
LED targets–not usable in SEL
OGIC
control equations
1
2HB1
Second-harmonic block asserted for differential element 1
19
2HB2
Second-harmonic block asserted for differential element 2
19
2HB3
Second-harmonic block asserted for differential element 3
19
32IE
Internal enable for the 32I element
20
32IF
32I element forward (internal) fault declaration
21
32IR
32I element reverse (external) fault declaration
21
49A01A
RTD1A alarm picked up (SEL-387-5 and SEL-387-6 Relays)
53
49A01B
RTD1B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
56
49A02A
RTD2A alarm picked up (SEL-387-5 and SEL-387-6 Relays)
53
49A02B
RTD2B alarm picked up (SEL-387-5 and SEL-387-6 Relays)
56
Table 4.10
Relay Word Bit Definitions
(Sheet 12 of 12)
Row
Bit
Definition
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...