Date Code 990430
Breaker/Recloser Monitor, Battery System Monitor,
8-19
Metering, and Load Profile Functions
SEL-351P Manual Técnico
Battery Status
You can check the battery status in several ways. On the front panel, the BATTERY PROBLEM
LED (see Figure 1.51) illuminates for any of the following battery problems:
•
Load test failure (Relay Word bit DTFAIL = logical 1)
•
Damaged or disconnected (battery cannot charge or discharge; Relay Word bit NO
BATT = logical 1)
•
Battery monitor/charger failure (Relay Word bit BCBOK = logical 0)
You also can press the STATUS pushbutton on the front panel of the SEL-351P to access more
battery status information. Use the secondary function up/down arrow pushbuttons to move to
different status screens. Those status elements of interest for the battery are the following:
MODE =
CHARGE - battery is charged
≥
90% (trickle charging)
HICHRG -
battery is charged < 90% (high charging)
DISCHRG - battery is discharging
DISTST -
battery load test in progress
NOBATT - battery is damaged or disconnected (it cannot
charge or discharge)
FAIL -
battery monitor/charger failed or
communications with the battery monitor/
charger are temporarily interrupted
%CAP =
0 to 100 -
battery charge level (independent of
temperature).
HRS_LFT =
hh:mm - hours and minutes left to run on battery in discharge
mode before the SEL-351P puts itself to sleep (dependent on
setting “% Battery capacity for sleep [0-100]”). Shows
XX:XX if battery is charging.
5V_PSBC
internal 5 V power supply level for battery monitor/charger.
12V_AUX
voltage level of 12 V auxiliary output – available via terminal
block positions 23 and 24 – controlled by two 12 V settings in
the EZ Level Global Settings.
VBAT =
voltage level of 24 V battery.
IBAT =
current level (in mA) at which the 24 V battery is charging or
discharging (preceded by a minus sign for discharging).
You can obtain the same battery status information as described above via serial port
communication using the STATUS command.
Additional Application
In addition to alarming, you can use the relay elements associated with the battery and charging
system to perform control functions, such as to disable or block reclosing. For example, the
factory default logic settings include the following automatic reclose supervision setting:
79CLS = TRCAP * CLCAP * BCBOK * !NOBATT * !DTFAIL
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......