5-6
Trip and Target Logic
Date Code 990215
SEL-351P Manual Técnico
Figure SECTION 5: .3:
Three-Pole Open Logic (top) and Switch-Onto-Fault Logic
(bottom)
Three-Pole Open Logic
Three-pole open (3PO) logic is the top half of Figure SECTION 5: .3. It is not affected by
enable setting ESOTF (see Settings Sheet 1 of 23 in
Section 9: Setting the SEL-351P Recloser
Control
).
The open circuit breaker condition is determined from the combination of:
•
Circuit breaker status (52A)
•
Load current condition (50L)
If the circuit breaker is open (52A = logical 0) and current is below phase pickup 50LP
(50L = logical 0), then the three-pole open (3PO) condition is true:
3PO = logical 1
(circuit breaker open)
The 3POD dropout time qualifies circuit breaker closure, whether detected by circuit breaker
status (52A) or load current level (50L). When the circuit breaker is closed:
3PO = logical 0
(circuit breaker closed)
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......