3.7
Date Code 20120126
Instruction Manual
SEL-2032 Communications Processor
Job Done Examples
Example 2: Using the SEL-2032 as a Port Switch
Step 5. Use
SET A
to define a timed trigger condition in the form of
(Thh:mm:ss) to send a date message, at a specific time once
each day, to the relay connected to Port 1. Skip Step 5 if you are
using an SEL-500 series, SEL-300 series, or SEL-400 series
relay with an IRIG-B input connected to the SEL-2032.
This setting sequence uses the
SET A
command to set a
message trigger and a message in Port 1 of the SEL-2032. This
example sets the SEL-2032 to issue the date command to the
relay attached to Port 1 once each day. Even though you supply
IRIG-B time to the relays, if a relay is powered down for any
reason, it may need this date information to establish the
current year because the year is not supplied by IRIG-B. The
date is retrieved from the SEL-2032 Global region and
formatted in a message string that the relay will recognize.
The SEL-2032 maintains date and time information in the
Global region. You can access this information using the
VIEW
command. Use the labels displayed by the
VIEW
command when you define the date message sequence with the
SET A
command. For an interpretation of the labels shown in
the
VIEW
screen and for a description of the Global region,
see
.
To see the Global data format, type
VIEW 1:GLOBAL
<Enter>
to display Global database information. Your screen
should look like the example in
.
*>>
VIEW 1:GLOBAL <Enter>
Port 1, Data Region GLOBAL Data
FID = FID=SEL-2032-R100-V0-Z000000-D20021222
STATUS = 0100h CONFIG = 0CA0h __YEAR = 1997 DAY_OF_YEAR = 304 (10/01)
MONTH = 10 DATE = 31 TIME = 14:12:03.598
ELEMENTS = 04h,00h,00h,20h,FFh,FFh,00h
REMOTE_BIT_REG = 0000h REMOTE_BITS = 00h _YEARS = 97
_HOURS = 14 _MINS = 12 _SECS = 3
CARD1_FID = FID=SEL-2711-R100-V0-D971031
CARD1_SERVICES = 64 CARD1_STATUS = 0021h CARD1_CONFIG = 0001h
CARD1_STEST_ERR = 0082h
CARD2_FID =
CARD2_SERVICES = 0 CARD2_STATUS = 0000h CARD2_CONFIG = 0000h
CARD2_STEST_ERR = 0000h PORT_STATUS = 0004h ALT_PORT = 255
NUM_MESGS = 20 BAD_MESGS = 0
*>>
Figure 3.5
Global Data Region Contents
Now, type
SET A 1
to define a timed trigger condition and a
message to send the date message to the relay connected to
Port 1 at a specific time once each day. Enter the information
and follow the prompts to set the SEL-2032 to match the
settings shown in
Содержание SEL-2032
Страница 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 12: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 46: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 70: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 104: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 244: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 322: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 328: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 338: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 342: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 348: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 354: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...