9.11
Date Code 20080918
Instruction Manual
SEL-749M Relay
Analyzing Events
Event Reporting
Event: Overcurrent Trip
IA IB IC IN IG
CURRENT MAG (A) 1148.5 98.7 100.0 0.04 1051.2
VAB VBC VCA
VOLTAGE MAG L-L (V) 4217 4215 4263
Winding Bearing Ambient Other
Hottest RTD(C): NA NA NA NA
RID := SEL-749M
TID := MOTOR RELAY
CTR1 := 100 FLA1 := 250.0 E2SPEED := N CTRN := 100
PTR := 35.00 VNOM := 4160 DELTA_Y := DELTA
E49MOTOR:= Y SETMETH := RATING 49RSTP := 75 SF := 1.15
LRA1 := 6.0 LRTHOT1 := 10.0 TD1 := 1.00 RTC1 := AUTO
TCAPU := 85 TCSTART := OFF COOLTIME:= 18 ETHMBIAS:= N
50P1P := 4.00 50P1D := 0.00 50P2P := OFF 50N1P := OFF
50N2P := OFF 50G1P := OFF 50G2P := OFF
LJTPU := OFF LJAPU := OFF
LLTPU := OFF LLAPU := OFF
46UBT := OFF 46UBA := 10 46UBAD := 10 PROTBL_T:= OFF
THERBL_T:= OFF
START_T := OFF
ESTAR_D := N
MAXSTART:= OFF TBSDLY := OFF ABSDLY := OFF
E47T := Y
SPDSDLYT:= OFF SPDSDLYA:= OFF
EPTC := N
E49RTD := Y RTD1LOC := OFF RTD2LOC := OFF RTD3LOC := OFF
RTD4LOC := OFF RTD5LOC := OFF RTD6LOC := OFF RTD7LOC := OFF
RTD8LOC := OFF RTD9LOC := OFF RTD10LOC:= OFF RTD11LOC:= OFF
RTD12LOC:= OFF
27P1P := 0.80 27P1D := 0.5 27P2P := OFF
59P1P := 1.10 59P1D := 0.5 59P2P := OFF
NVARTP := OFF PVARTP := OFF NVARAP := OFF PVARAP := OFF
37PTP := OFF 37PAP := OFF
55LGTP := OFF 55LDTP := OFF 55LGAP := OFF 55LDAP := OFF
81D1TP := OFF 81D1AP := OFF
81D2TP := OFF
81D2AP := OFF
LOAD := OFF
AOPARM := LOAD_I
BLKPROT := 0
BLK46 := N BLK48 := N BLK50EF := N BLK50P := N
BLK37 := N BLK66 := N BLK49PTC:= N BLK49RTD:= N
TDURD := 0.5
TR := 49T OR LOSSTRIP OR JAMTRIP OR 46UBT OR 50P1T OR 50G1T OR 59P1T OR 47T
OR 55T OR SPDSTR OR 50N1T OR SMTRIP OR 81D1T OR 81D2T OR SV01T
REMTRIP := 0
ULTRIP := 0
52A := NOT IN101
STREQ := 0
EMRSTR := IN102 AND STOPPED
SPEED2 := 0
SPEEDSW := 0
Report Settings
SER1 := IN101 IN102 NOSLO THERMLO
SER2 := 49T LOSSTRIP JAMTRIP 46UBT 50P1T RTDT PTCTRIP 50G1T VART 37PT 27P1T
59P1T 47T 55T SPDSTR 50N1T SMTRIP 81D1T 81D2T OTHTRIP
SER3 := AMBTRIP PTCFLT RTDFLT COMMIDLE COMMLOSS REMTRIP RSTTRGT 49A LOSSALRM
JAMALRM 46UBA RTDA 55A 50N2T 50G2T VARA 37PA 27P2T 59P2T
SER4 := SPDSAL 81D1A 81D2A OTHALRM AMBALRM SALARM WARNING LOADUP LOADLOW
50P2T STOPPED RUNNING STARTING STAR DELTA START SPEED2
ER := R_TRIG 50P1T
LER := 15 PRE := 5 MSRR := 5
Figure 9.3
Example Standard 15-Cycle Event Report 1/4-Cycle Resolution
Содержание SEL-749M
Страница 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 14: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 20: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 52: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 118: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 224: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 286: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 306: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 310: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 314: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...