12.7
Date Code 20090730
Instruction Manual
SEL-734 Meter
Testing and Troubleshooting
Testing Methods and Tools
To Set Test Constant (KET)
Step 1. From the TEST mode options display, use the
DOWN ARROW
pushbutton to select
Watthour Constant
on the front-panel
display.
Step 2. Press
ENT
to display the KET setting.
Step 3. Press
ENT
to edit the setting.
Step 4. Use the
RIGHT ARROW
and
LEFT ARROW
pushbuttons to select the
digit to be edited.
Step 5. Use the
UP ARROW
and
DOWN ARROW
pushbuttons to increment
and decrement each digit as necessary.
Step 6. When KET is set to the desired constant, press
ENT
.
Step 7. At the
Save Settings?
prompt, select
YES
to save settings or
NO
to abort changes and press
ENT
.
NO
is selected by default.
Step 8. If
YES
is selected and
ENT
pressed, the front-panel displays
Settings Saved
. Press the
ESC
pushbutton twice to return to
the display of TEST mode options.
Exiting TEST Mode
Any one of the following causes the SEL-734 to exit TEST mode:
➤
Press the
ESC
button on the front of the meter twice from the
display of TEST mode options.
➤
TEST mode will automatically time out at a predefined point
adjusted by FP_TO. Setting FP_TO to OFF will disable
automatic time-out and require a manual exit from TEST mode.
➤
Power loss while in TEST mode restores normal operating
conditions.
Pressing the
RESET
pushbutton at anytime in TEST mode does
the following:
➢
Resets the FP_TO timer.
➢
Resets data accumulations to zero.
Table 12.2
Default Meter Test Pulse Weights
If the Value Displayed Is:
The Test Pulse Output Is:
Watts or Watt-hours, per phase or total,
in or out
Watt-hours, per phase or total, in or out,
1.8 Wh/pulse
VARs or VAR-hours, per phase or total,
in or out
VAR-hours, per phase or total, in or out,
1.8 VARh/pulse
VAs or VA-hours, per phase or total,
in or out
VA-hours, per phase or total, in or out,
1.8 VAh/pulse
Содержание SEL-734
Страница 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 18: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 44: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 98: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 146: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 170: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 206: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 230: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 344: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...