D.18
SEL-700G Relay
Instruction Manual
Date Code 20170814
DNP3 Communications
DNP3 Documentation
Device Profile
The DNP3 Device Profile document, available on the supplied CD or as a
download from the SEL website, contains the standard device profile
information for the SEL-700G. This information is also available in XML
format. Please refer to this document for complete information on DNP3
Protocol support in the SEL-700G.
Reference Data Map
Table D.10 shows the SEL-700G reference data map. The reference map
shows the data available to a DNP3 master. You can use the default map or the
custom DNP3 mapping functions of the SEL-700G to retrieve only the points
necessary for your application.
The SEL-700G scales analog values by the indicated settings or fixed scaling
indicated in the description. Analog dead bands for event reporting use the
indicated settings, or ANADBM if you have not specified a setting.
101
1
Small Packed Binary-Coded Decimal
101
2
Medium Packed Binary-Coded Decimal
101
3
Large Packed Binary-Coded Decimal
110
all
Octet String
111
all
Octet String Event
112
All
Virtual Terminal Output Block
113
All
Virtual Terminal Event Data
N/A
No object required for the following function
codes:
13 cold start
14 warm start
23 delay measurement
13, 14, 23
a
Supported in requests from master.
b
May generate in response to master.
c
Decimal.
d
Hexadecimal.
e
Default variation.
f
Default variation specified by serial port setting DVARAI (or DVARAIn for Ethernet session n [n = 1, 2, or3]).
Table D.9
SEL-700G DNP Object List
(Sheet 6 of 6)
Obj.
Var.
Description
Request
a
Response
b
Funct.
Codes
c
Qual. Codes
d
Funct.
Codes
c
Qual. Codes
d
Table D.10
DNP3 Reference Data Map
(Sheet 1 of 2)
Object
Labels
Description
Binary Inputs
01, 02
STFAIL
Relay Diagnostic Failure
STWARN
Relay Diagnostic Warning
STSET
Relay Settings Change or Relay Restart
Enabled–TLED_06
a
Relay Word Elements Target Row 0 (see Table J.1)
50PX1P–59V1X6T
Relay Word Elements (see Table J.1)
PFL_X
X-Side Power Factor Leading for Three-Phase
Currents
PFL_Y
Y-Side Power Factor Leading for Three-Phase
Currents
0
Logical 0
1
Logical 1
NOTE:
Dead-band changes via
Object 34 are not stored in nonvolatile
memory. Make sure to reissue the
Object 34 dead bands after a warm
(
STA C
) or cold start (power cycle).
NOTE:
Although the reference maps
do not show Relay Word bit labels, you
can use any Relay Word bit label for
creating custom maps.
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...