7.40
SEL-700G Relay
Instruction Manual
Date Code 20170814
Communications
SEL ASCII Protocol and Commands
If the requested SER report rows do not exist, the relay responds with
No SER
data
.
SER D Command
The SER D command shows a list of SER items that the relay has automatic-
ally removed. These are “chattering” elements. You can automatically remove
chattering SER elements in the SER Chatter Criteria category of the Report
settings; the enable setting is ESERDEL. See Section 4: Protection and Logic
Functions, Report Settings (SET R Command) for more information on SER
automatic deletion and reinsertion.
If you issue the SER D command and you have not enabled automatic
removal of chattering SER elements (Report setting ESERDEL), the relay
responds,
Automatic removal of chattering SER elements not enabled
.
SET Command (Change Settings)
The SET command is for viewing or changing the relay settings (see
Table 7.45 and Table 7.46).
date1
Append date1 to return all rows with this date. For example, use SER
1/1/2003 to return all records for January 1, 2003.
date1 date2
Append date1 and date2 to return all rows between date1 and date
beginning with date1 and ending with date2. Enter the oldest date
first to display a chronological progression through the report. Enter
the newest date first to display a reverse chronological progression.
Date entries are dependent on the date format setting DATE_F. For
example, use SER 1/5/2003 1/7/2003 to return all records for
January 5, 6, and 7, 2003.
Table 7.43
SER Command Format
(Sheet 2 of 2)
Parameter
Description
Table 7.44
SER D Command
Command
Description
Access Level
SER D
List chattering SER elements that the relay is
removing from the SER records.
1
Table 7.45
SET Command (Change Settings)
Command
Description
Access Level
SET n s TERSE
Set the Relay settings, beginning at the first
setting for group n (n = 1, 2, or 3).
2
SET L n s TERSE
Set general logic settings for group n
(n = 1, 2, or 3).
2
SET G s TERSE
Set global settings.
2
SET P n s TERSE
Set serial port settings. n specifies the
PORT
(
1
,
2
,
3
,
4
, or
F
); n defaults to the active port if not
listed.
2
SET R s TERSE
Set report settings such as Sequential Events
Recorder (SER) and Event Report (ER)
settings.
2
SET F s TERSE
Set front-panel settings.
2
SET M s TERSE
Set Modbus User Map settings.
2
SET DNP m s TERSE
Set DNP Map m settings where m = 1, 2, or 3
2
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...