4.235
Date Code 20170814
Instruction Manual
SEL-700G Relay
Protection and Logic Functions
Report Settings (SET R Command)
You can enable or disable the auto-deletion function via the SER settings. Any
auto-deletion notice entry is lost during changes of the settings. The deleted
items can be viewed in the SER Delete Report (command SER D—refer to
Section 7: Communications for additional information).
SER Trigger Lists
To capture element state changes in the SER report, enter the Relay Word bit
into one of the four SER (SER1 through SER4) trigger equations. Each of the
four programmable trigger equations allows entry of as many as 24 Relay
Word bits separated by spaces or commas; the SER report accepts a total of 96
Relay Word bits. Table 4.92 shows the settings prompt and the default settings
for the four SER trigger equations.
Relay Word Bit
Aliases
To simplify your review of the information displayed in the SER record, the
relay provides the Alias setting function. Using the Alias settings, you can
change the way relay elements listed previously in the SER settings are
displayed in the SER report. In addition, the Alias settings allow you to
change the text displayed when a particular element is asserted and deasserted.
The relay permits as many as 20 unique aliases, as defined by the Enable Alias
Settings (EALIAS) setting. Factory-default alias settings are shown in
Table 4.94.
Define the Enabled ALIAS settings by entering the Relay Word bit name, a
space, your alias, a space, the text to display when the condition asserts, a
space, and the text to display when the condition deasserts.
See Table J.1 for the complete list of Relay Word bits. Use as many as
15 characters to define the alias, asserted text, and deasserted text strings. You
can use capital letters (A–Z), numbers (0–9), and the underscore character (_)
within each string. Do not attempt to use a space within a string, because the
relay interprets a space as the break between two strings. To clear a string,
simply type NA.
Table 4.92
SER
a
Trigger Settings
a
Use as many as 24 Relay Word elements separated by spaces or commas for each setting.
Setting Prompt
Setting Name :=
SER1
SER1 := IN101 IN102 PB01 PB02 PB03 PB04 52AX 52AY
TRIPX TRIPY TRIP1 TRIP2 TRIP3
SER2
SER2 := ORED51T ORED50T 87U 87R OOST 21C1T 21C2T
3PWRX1T 3PWRX2T 3PWRY1T 3PWRY2T REF1F REF1R
24D1T 24C2T RTDT
SER3
SER3 := 64G1T 64G2T 64F1T 64F2T 46Q1T 46Q2T LOPX
LOPY 81X1T 81X2T 81Y1T 81Y2T
SER4
SER4 := SALARM 49T 40Z1T 40Z2T
Table 4.93
Enable Alias Settings
Setting Prompt
Setting Range
Setting Name =
Enable ALIAS Settings (N, 1–20)
N, 1–20
EALIAS := 4
ALIAS1 = PB01 FP_AUX1 PICKUP DROPOUT
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...