4.219
Date Code 20170814
Instruction Manual
SEL-700G Relay
Protection and Logic Functions
Port Settings (SET P Command)
Access Control
The DSABLSET setting defines conditions for disabling all setting changes
from the front-panel interface. To disable setting changes from the front-panel
interface, assign, for example, a contact input (for example, DSABLSET :=
IN402) to the DSABLSET setting. When Relay Word bit DSABLSET asserts,
you can view the device settings from the front-panel interface, but you can
only change the settings by using serial port commands. Table 4.72 shows the
settings prompt, the setting range, and the factory-default settings.
Time Synchronization
Source
The SEL-700G accepts a demodulated IRIG-B time signal. Table 4.73 shows
the setting to identify the input for the signal. Set TIME_SRC := IRIG1 when
you use relay terminals B01/B02 or EIA-232 serial Port 3 for the time signal
input. When you use fiber-optic Port 2 for the signal, set the
TIME_SRC := IRIG2. Refer to IRIG-B Time-Code Input on page 2.21 and
IRIG-B on page 7.5 for additional information.
Port Settings (SET P Command)
The SEL-700G provides the settings that allow you to configure the
parameters for the communications ports. See Section 2: Installation for a
detailed description of port connections. On the base unit,
Port F
(front panel)
is an EIA-232 port;
Port 1
is an optional Ethernet port(s);
Port 2
is an optional
fiber-optic serial port; and
Port 3
(rear) can be an EIA-232 or an EIA-485 port.
On the optional communications card, you can select
Port 4
as either EIA-485
or EIA-232 (not both) with the COMMINF setting. See Table 4.74 through
Table 4.79 for the port settings, also see Appendix D: DNP3 Communications,
Appendix E: Modbus RTU Communications, Appendix F: IEC 61850
Communications, Appendix G: DeviceNet Communications, Appendix H:
Synchrophasors, and Appendix I: M
Communications) for
additional information on the protocol of interest.
RESET DEMAND
SEL
OGIC
RSTDEM := 0
RESET PK DEMAND
SEL
OGIC
RSTPKDEM := 0
Table 4.71
Data Reset Settings
(Sheet 2 of 2)
Setting Prompt
Setting Range
Setting Name :=
Factory Default
Table 4.72
Setting Change Disable Setting
Setting Prompt
Setting Range
Setting Name :=
Factory Default
DISABLE SETTINGS
SEL
OGIC
DSABLSET := 0
NOTE:
DSABLSET does not disable
the setting changes from the serial
ports.
Table 4.73
Time Synchronization Source Setting
Setting Prompt
Setting Range
Setting Name :=
Factory Default
IRIG TIME SOURCE
IRIG1, IRIG2
TIME_SRC := IRIG1
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...