4.110
SEL-700G Relay
Instruction Manual
Date Code 20170814
Protection and Logic Functions
Group Settings (SET Command)
Figure 4.77
Negative-Sequence Voltage-Polarized Directional Element for
Residual-Ground Overcurrent Elements
q
From Table 4.28
w
To Figure 4.81
e
From Figure 4.74
I
2
V
2
If Z2F Setting
>
0, Forward Threshold = 1.25 • Z2F — 0.25 •
I
2
V
2
If Z2F Setting
≤
0, Forward Threshold = 0.75 • Z2F — 0.25 •
Forward Threshold:
I
2
V
2
If Z2R Setting
<
0, Reverse Threshold = 1.25 • Z2R + 0.25 •
I
2
V
2
If Z2R Setting
≥
0, Reverse Threshold = 0.75 • Z2R + 0.25 •
Reverse Threshold:
Direction Element Characteristics
R2
X2
Forward Threshold
Reverse Threshold
Z2 PLANE
DIRQGE is highest
RDIRQG
(Reverse)
FDIRQG
(Forward)
Best Choice
Ground
Directional
Logic
50QF
Enable
Forward
Threshold
DIRQGE
Reverse
Threshold
50QR
e
Re[V
2
•(I
2
•1
∠
Z1ANG)*]
|I
2
|
2
Z2 =
I
2
V
2
Relay
Word
Bits
Relay
Word
Bit
Relay
Word
Bit
Relay
Word
Bit
choice that is asserted
1
2
3
3
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...