5.2
SEL-587Z Instruction Manual
Date Code 20020903
Setting the Relay
Settings Changes Via the Serial Port
Settings Changes Via the Serial Port
NOTE:
In this manual, commands
you type appear in bold/uppercase:
SHOWSET
. You need to type only the
first three letters of a command, for
example,
SHO
. Computer keys you
press appear in bold/uppercase/
brackets:
<Enter>
. Relay front-panel
pushbuttons you press appear in
bold/uppercase/curly brackets:
{EVENTS}
.
See
Section 6: Serial Port Communications
for information on serial port
communications and relay access levels. To change a specific setting, enter
the command:
SET
n s
where
n
= L, P, T, or R (parameter
n
is not entered for the Relay settings) and
s
is the name of the specific setting you want to access and begin setting. If
s
is
not entered, the relay starts at the first setting. For example, to set Event
Report 1, type the following:
SET L ER1 <Enter>
The relay responds with:
ER1 = 87A1+87B1+87C1
?
If you omit the
s
parameter, the relay starts at the top of the logic settings and
responds with the following:
TR1 = 87A1+87B1+87C1
?
When you issue the
SET
n
command, the relay starts at the top of the
particular setting group and presents a setting. Enter a new setting and press
<
Enter
>; if you want to retain the existing setting, then press <
Enter
> only.
After the
<Enter>
keystroke, the relay presents the next setting, and so on.
shows the editing keystrokes.
The relay checks each entry to ensure that it is within the setting range. When
out of range, the relay generates an “Out of Range” message and prompts for
the setting again.
When settings are complete, the relay displays the new settings and prompts
for approval to enable them. Answer
Y
<Enter>
to enable the new settings.
While the active settings are updated (about one second), the relay is disabled,
and the ALARM contact closes.
Table 5.1
SET Command Editing Keystrokes
Press Key(s)
Results
<Enter>
Retains setting and moves to the next
^ <Enter>
Returns to previous setting
< <Enter>
Returns to previous setting
> <Enter>
Moves to next setting
END<Enter>
Exits editing session, then prompts you to save the settings
<CTRL> X
Aborts editing session without saving changes
Содержание SEL-587Z
Страница 10: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 66: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 126: ...This page intentionally left blank ...
Страница 162: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 260: ...This page intentionally left blank ...