Date Code 20020903
SEL-587Z Instruction Manual
Section 9
Event Reports and SER
Introduction
Analyze events with event report summaries and event reports. For example,
selecting an event report with the
EVE L
command provides a report with
15 cycles of input voltages, input currents, high-impedance elements,
overcurrent elements, inputs and outputs with 1/8-cycle data resolution,
summary report, and settings.
Full-length event reports are stored in nonvolatile memory for later retrieval.
Software programs such as the SEL-5601 Analytic Assistant convert the event
report data to oscillography. Use the
HISTORY
command to obtain an index
of these stored reports.
Enable automatic messaging to configure the SEL-587Z Relay to send event
report summaries of the serial port and to a printer, for example, to obtain a
hard copy at the instant the report is triggered.