Instruction Manual
SEL-400 Series Relays
Instruction Manual
Instruction Manual
S E C T I O N
5
Control
SEL-400 series relays provide many control features, including circuit breaker
controls, disconnect controls, remote bit controls, and bay control. This section
describes these control capabilities.
➤
Circuit Breaker Status and Control on page 5.1
➤
➤
➤
Bay Control Front-Panel Operations on page 5.12
➤
QuickSet Bay Control Screens on page 5.27
➤
Customizable Screens on page 5.34
➤
Bay Control Example Application on page 5.35
See the specific relay instruction manuals to see how many breakers, disconnects,
and remote bits are available and to determine whether or not bay control is sup-
ported.
Circuit Breaker Status and Control
SEL-400 series relays include circuit breaker status logic for all supported circuit
breakers. The circuit breaker status logic uses the 52A_
k
setting (SEL
OGIC
equa-
tion) and open-phase detection logic to determine the state of Circuit Breaker
k
,
and declare Circuit Breaker
k
alarm conditions. See
Section 5: Protection
of the
product-specific instruction manual for a description of circuit breaker status
logic Relay Word bits and circuit breaker status logic diagrams.
SEL-400 series relays support opening and closing breakers. These operations
can be controlled via the terminal commands
OPEN
and
CLOSE
, the binary ter-
minal Fast Operate messages, various supported communications protocols, the
front-panel menus, and through the bay control one-line screens. These controls
operate the open control (OC
k
) and close control (CC
k
) bits. These bits are used
in the relay trip and close logic to integrate these external controls with the relay
automatic trip and close behavior. See
Section 6: Protection Application Exam-
ples
in the product-specific instruction manual for more information on the trip
and close logic.
Disconnect Logic
Disconnect Switch Close and Open Control Logic
shows the Disconnect Logic that generates open and
close output signals necessary to perform the open and close disconnect opera-
tions. Use the seal-in timers (89CST
m
and 89OST
m
) to monitor and control dis-
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...