3.13
Date Code 20171021
Instruction Manual
SEL-421 Relay
Testing
Checking Relay Operation
The result of
is an impedance magnitude that varies with the magni-
tude and angle of the applied current. Normally, a forward fault results in a nega-
tive Z2c relay calculation.
Test Current
Solve
to find the test current values that you need to apply to the
relay to test the element. For the negative-sequence current I
2
, the result is
Equation 3.2
when:
Equation 3.3
Multiply the quantities in
by three to obtain 3I
2
, the negative-
sequence current that the relay processes. With a fixed applied negative-sequence
voltage V
A
, the relay negative-sequence voltage is 3V
2
. Set Z2c = Z2F to find the
test current magnitude at the point where the impedance calculation equals the
forward fault impedance threshold.
becomes:
Equation 3.4
when:
Equation 3.5
For a reverse fault impedance threshold, where Z2c = Z2R,
becomes:
Equation 3.6
when the angle calculation is the same as
.
For more information on the directional elements, see
and
Quadrilateral Ground-Distance Elements on page 1.18
.
For settings and application information, see
Section 6: Protection Applications
.
Checking the Negative-Sequence Directional Element (Phase Faults)
This test confirms operation of the F32Q and the R32Q negative-sequence direc-
tional elements. This test procedure is for a 5 A relay; scale values appropriately
for a 1 A relay.
I
2
V
2
Z2c
----------
=
I
2
V
2
Z1ANG
–
=
I
TEST
3I
2
3V
2
Z2c
-------------
3V
2
Z2F
-------------
=
=
=
I
TEST
3I
2
3V
2
Z1ANG
–
=
=
I
TEST
3I
2
3V
2
Z2c
-------------
3V
2
Z2R
-------------
=
=
=
NOTE:
As you perform this test,
other protection elements can assert.
This causes the relay to assert other
targets and possibly close control
outputs. Be sure to isolate the relay
from the power system to avoid
unexpected system effects.
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...