12.20
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Settings
Alias Settings
For an analog display point, the syntax is:
Analog name, "User Text and Formatting", "Text Size"
See the Front-Panel Operations section for more information on configuring dis-
play points.
Local control bits are configured using the Local Control category. This is a
freeform category. Each entry has the following syntax:
Local bit name, "Label", "Set State", "Clear State", Pulse enable
for more information on configuring local con-
trol bits.
Alias Settings
Although SEL-400 series relays provide extensive programming facilities and
opportunity for comments, troubleshooting customized programs is sometimes
difficult. Aliases provide an opportunity to assign more meaningful names to the
generic variable names to improve the readability of the program. These aliases
can be used in settings and SEL
OGIC
equations and are used in most relay reports.
Assign a valid seven-character alias name to any Relay Word bit or any Analog
Quantity. (Some SEL-400 series relays support aliasing additional types of data.)
Invalid alias names include the following keywords used by settings and
SEL
OGIC
control equations:
➤
END
➤
INSERT
➤
DELETE
➤
LIST
➤
NA
➤
OFF
SEL
OGIC
control equation operators (e.g., NOT, AND, OR, COS) cannot be used
as alias names. A quantity may only be assigned one alias. An alias cannot match
an existing relay word or analog quantity name.
Alias names are valid when the following are true:
➤
They consist of a maximum of seven characters.
➤
They are constructed using characters 0–9, uppercase A–Z, or the
underscore (_).
Table 12.32
Local Bit SEL
OGIC
a
a
appear if the associated local bit is defined. If no local bits are
defined, the whole category is hidden.
Label
Prompt
Default Value
LB_SPmm
Local Bit Supervision (SEL
OGIC
Equation, NA)
1
LB_DPmm
Local Bit Status Display (SEL
OGIC
Equation, NA)
LBmm
Table 12.33
SER Parameters
Label
Prompt
Default Value
SER_PP
Five Events per SER Events page? (Y for 5, N for 3)
N
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...