12.19
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Settings
Front-Panel Settings
Boolean display points are selected using freeform settings fields. Two types of
display points can be entered: Boolean and analog. For Boolean display points,
the entry syntax is:
Bit name, "Label", "Set String", "Clear String", Text Size"
STA_BAT
Station Battery Screen (Y,N)
N
FUND_VI
Fundamental Voltage and Current Screen (Y,N)
Y
FUNDSEQ
Fundamental Sequence Quantities Screen (Y,N)
N
FUND_BK
Fundamental Breaker Currents Screen (Y,N)
N
DIFF_L
Differential Metering Local Currents Screen (Y,N)
Y
DIFF_T
Differential Metering Total Currents Screen (Y,N)
Y
DIFF
Differential Metering (Y,N)
Y
ZONECFG
Terminals Associated with Zones (Y,N)
Y
Table 12.30
Selectable Operator Pushbuttons
Label
Prompt
Default Value
PB1_HMI
Pushbutton 1 HMI Screen (OFF,AP,DP,EVE,SER)
a,
b
a
PB
n
_HMI can only be set to DP if a valid display point has been set.
b
Each instance (AP, DP, EVE, SER) can only be set to a single operator pushbutton.
OFF = No HMI Pushbutton Operation
AP = Alarm Points
DP = Display Points
EVE = Event Summaries
SER = SER HMI Display
OFF
PB2_HMI
Pushbutton 2 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB3_HMI
Pushbutton 3 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB4_HMI
Pushbutton 4 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB5_HMI
Pushbutton 5 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB6_HMI
Pushbutton 6 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB7_HMI
Pushbutton 7 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB8_HMI
Pushbutton 8 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB9_HMI
c
c
PB9–PB12 settings are only available on 12-pushbutton models.
Pushbutton 9 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB10HMI
Pushbutton 10 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB11HMI
Pushbutton 11 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
PB12HMI
Pushbutton 12 HMI Screen (OFF,AP,DP,EVE,SER)
OFF
Table 12.31
Front-Panel Event Display
Label
Prompt
Default Value
DISP_ER
Enable HMI Auto Display of Events Summaries (Y,N)
Y
TYPE_ER
Types of Events for HMI Auto Display (ALL,TRIP)
a
a
Setting is only available if DISP_ER := Y.
ALL
NUM_ER
Operator Pushbutton Events to Display (1–100)
b
b
Setting is only available if an operator pushbutton has been set to EVE.
10
c
c
Some relays default NUM_ER to 3.
Table 12.29
Selectable Screens for the Front Panel (Sheet 2 of 2)
Label
Prompt
Default Value
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...