3-6
Differential, Restricted Earth Fault,
Date Code 20020129
Overcurrent, Voltage, and Frequency Elements
SEL-387E Instruction Manual
Common (Cross) or Independent Blocking
Use common or independent blocking elements (87BL1, 87BL2, and 87BL3) to supervise the
restrained differential elements. Common blocking disables all restrained elements if any
blocking element is picked up. Figure 3.5 shows how independent blocking disables the
restrained element associated with the blocking element.
If IHBL is set to N (No), the logic shown in Figure 3.5 to the left of the vertical line, IHBL = N,
is enabled. In this case all 87Rn elements enter one OR gate, and all 87BLn elements enter
another OR gate, whose output is negated at the upper AND gate. If the 87Rn OR output asserts
but the 87BLn OR output does not, the 87R Relay Word bit asserts and tripping can take place.
In other words, with IHBL = N, blocking within ANY differential element will prevent operation
and tripping of ALL the restrained differential elements.
$,+%/ 1
&RPPRQ+DUPRQLF%ORFNLQJ
,QGHDUPRQLF%ORFNLQJ
5
5
5
%/
%/
%/
5
%/
%,+%/ <
':*0
5
%/
5
%/
5
%/
5
%/
Figure 3.5: Differential Element Harmonic Blocking Logic
If IHBL is set to Y (Yes), the logic shown in Figure 3.5 to the right of the vertical line, IHBL =
Y, is enabled. Here, the logic pairs 87R1 with negated 87BL1, 87R2 with negated 87BL2, and
87R3 with negated 87BL3 at separate AND gates. In this logic, blocking in a given element will
only disable tripping of that element. In general, this mode of operation might only be used
where three single-phase transformers are used to make up a three-phase bank, and independent-
pole breaker operation is possible, in the harmonic blocking mode. When harmonic restraint is
selected, the relay operates only in the individual blocking mode.
Relay Word bits 87R and 87U are high-speed elements that must trip all breakers. Our example
assigns 87R and 87U to trip variable setting TR4. If either bit asserts, this variable asserts bit
TRIP4, which drives contact OUT104. OUT104 connects to an 86 lockout device, which trips all
breakers via multiple sets of contacts.
Harmonic
Blocking
Figure 3.6 shows how the 87BL1 blocking element will pick up if the second-, fourth-, or fifth-
harmonic operating current, as a percentage of fundamental operating current, are above the
2PCT, 4PCT, or 5PCT setting thresholds, respectively. The blocking element will also pick up if
the ratio of positive and negative dc exceeds a threshold as shown in Figure 3.7. The blocking
prevents improper tripping during transformer inrush or allowable overexcitation conditions.
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......