Date Code 20020215
Overcurrent, Voltage, Synchronism Check, and Frequency Elements
3-7
SEL-351R Instruction Manual
If instantaneous overcurrent elements are made directional, the pickup time curve in Figure 3.5 is
adjusted as follows:
multiples of pickup setting
≤
4: add 0.25 cycle
multiples of pickup setting > 4: add 0.50 cycle
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.2
2
3
4
5
6
7
8
9
10
Applied Current (Multiples of Pickup Setting)
Pic
kup Tim
e (
C
yc
le
s)
Maximum
Minimum
Figure 3.5: SEL-351R Recloser Control Nondirectional Instantaneous Overcurrent
Element Pickup Time Curve
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
1.2
2
3
4
5
6
7
8
9
10
Applied Current (Multiples of Pickup Setting)
Re
se
t Tim
e (Cyc
le
s)
Maximum
Minimum
Figure 3.6: SEL-351R Recloser Control Nondirectional Instantaneous Overcurrent
Element Reset Time Curve
Phase-to-Phase Instantaneous Overcurrent Elements
Four levels of phase-to-phase instantaneous overcurrent elements are available. The different
levels are enabled with the E50P enable setting, as shown in Figure 3.7.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......