Date Code 20020215
Serial Port Communications and Commands
10-47
SEL-351R Instruction Manual
The control generates an event report if any of the OUT101 through OUT107 contacts are
pulsed. The PULSE command is primarily used for testing purposes.
Access Level 2 Commands
Access Level 2 commands allow unlimited access to recloser control settings, parameters, and
output contacts. All Access Level 1, Access Level E (EZ), and Access Level B commands are
available from Access Level 2. The screen prompt for Access Level 2 is: =>>
CON Command (Control Remote Bit)
The CON command is a two-step command that allows you to control Relay Word bits RB1
through RB8 (RB1 through RB16 in the SEL-351R-2). See Row 26 and Row 59 in Table 9.4.
At the Access Level 2 prompt, type CON, a space, and the number of the remote bit you wish to
control, 1–8 (1–16 in the SEL-351R-2). The control responds by repeating your command
followed by a colon. At the colon, type the Control subcommand you wish to perform (see
Table 10.7).
The following example shows the steps necessary to pulse Remote Bit 5 (RB5):
=>>CON 5 <ENTER>
CONTROL RB5: PRB 5 <ENTER>
=>>
You must enter the same remote bit number in both steps in the command. If the bit numbers do
not match, the recloser control responds “Invalid Command.”
Table 10.7: SEL-351R Recloser Control Remote Bit Control Subcommands
Subcommand Description
SRB n
Set Remote Bit n (“ON” position)
CRB n
Clear Remote Bit n (“OFF” position)
PRB n
Pulse Remote Bit n for 1/4 cycle (“MOMENTARY” position)
See
Remote Control Switches
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for more information.
COP m n Command (Copy Setting Group)
You can copy EZ, Group, and SEL
OGIC
control equation settings from setting Group
m
to
setting Group
n
with the COPY command,
COP m n
. Setting group numbers range from 1 to 6.
After entering settings into one setting group with the SET and SET L commands, copy them to
the other groups with the COP command. Use the SET, SET EZ, and SET L commands to
modify the copied settings. The ALARM output pulses if you copy settings into the active
group.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......