7-16
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20020215
SEL-351R Instruction Manual
Figure 7.14: Latch Control Switch Operation Time Line
Use a Remote Bit Instead to Enable/Disable the Reclosing Relay
Use a remote bit to enable/disable the reclosing relay, instead of an optoisolated input. For
example, substitute remote bit RB1 for optoisolated input IN104 in the settings accompanying
Figure 7.13:
SET1 = /RB1 * !LT1
[= (rising edge of remote bit RB1) AND NOT(LT1)]
RST1 = /RB1 * LT1
[= (rising edge of remote bit RB1) AND LT1]
79DTL = !LT1
[= NOT(LT1); drive-to-lockout setting]
Pulse remote bit RB1 to enable reclosing, pulse remote bit RB1 to disable reclosing, etc.—much
like the operation of optoisolated input IN104 in the previous example. Remote bits RB1
through RB8 (RB1 through RB16 for the SEL-351R-2) are operated through the serial port. See
Figure 7.9 and
Section 10: Serial Port Communications and Commands
for more information
on remote bits.
These are just a few control logic examples—many variations are possible.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......