6.9
Date Code 20080213
Instruction Manual
SEL-351A Relay
Close and Reclose Logic
Reclose Supervision Logic
Factory Settings
Example
Refer to the top of
The factory setting for the SEL
OGIC
control equation reclose supervision
setting is:
79CLS =
1
(numeral 1)
The factory setting for the Reclose Supervision Limit Timer setting is:
79CLSD =
0.00 cycles
Any time a reclosing relay open interval times out, it propagates immediately
through
, because SEL
OGIC
control
equation setting 79CLS is always asserted to logical 1. Effectively, there is no
special reclose supervision.
Additional Settings
Example 1
Refer to the top of
SEL-351A relays are installed at both ends of a transmission line in a high-
speed reclose scheme. After both circuit breakers open for a transmission line
fault, the SEL-351A(1) Relay recloses circuit breaker 52/1 first, followed by
the SEL-351A(2) Relay reclosing circuit breaker 52/2, after a synchronism
check across circuit breaker 52/2.
NOTE:
Does not apply to the
SEL-351A-1.
Figure 6.4
SEL-351A Relays Installed at Both Ends of a Transmission Line
in a High-Speed Reclose Scheme
SEL-351A(1) Relay
Before allowing circuit breaker 52/1 to be reclosed after an open interval time-
out, the SEL-351A(1) Relay checks that Bus 1 voltage is hot and the
transmission line voltage is dead. This requires reclose supervision settings:
79CLSD =
0.00 cycles
(only one check)
79CLS =
3P59 * 27S
SEL-351A(2) Relay
The SEL-351A(2) Relay checks that Bus 2 voltage is hot, the transmission
line voltage is hot, and in synchronism after the reclosing relay open interval
times out, before allowing circuit breaker 52/2 to be reclosed. This requires
reclose supervision settings:
79CLSD =
0.00 cycles
(only one check)
79CLS =
25A1
SEL-351A (1)
Bus 1
Bus 2
52
1
52
2
IA, IB, IC
VA, VB, VC VS
SEL-351A (2)
IA, IB, IC
VA, VB, VC
VS
3-Phase
3-Phase
1-Phase
where:
3P59 = all three Bus 1 phase voltages (VA, VB, and VC) are hot
27S = monitored single-phase transmission line voltage (channel
VS
) is dead
Содержание SEL-351A
Страница 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...