13.4
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Testing and Troubleshooting
Testing Methods and Tools
Testing Methods and Tools
Test Features
Provided by the Relay
The features shown in
assist you during relay testing.
Low-Level Test
Interface
The SEL-351 has a low-level test interface between the calibrated input
module (output
J1
) and the separately calibrated processing module (input
J10
). You may test the relay in either of two ways:
➤
conventionally, by applying ac current signals to the relay
inputs
➤
or by applying low magnitude ac voltage signals to the low-
level test interface of the processing module (input
J10
).
Access the test interface of the processing module by removing the relay front
panel.
shows the location of the processing module input connector (
J10
)
for low-level test interface connections. The output connector (
J1
) of the input
module is below connector
J10
.
shows the low-level test interface (
J1
and
J10
) connector
information.
shows the output (
J1
) value of the input module (for a
given input value into the relay rear panel). The processing module input (
J10
)
Table 13.1
Helpful Commands for Relay Testing
Command
Description
METER
Command
The
METER
command shows the ac currents and voltages
(magnitude and phase angle) presented to the relay in primary
values. In addition, the command shows power system fre-
quency (FREQ) and the voltage input to the relay power supply
terminals (VDC). Compare these quantities against other
devices of known accuracy. The
METER
command is avail-
able at the serial ports and front-panel display. See
Serial Port Communications and Commands
and
EVENT
Command
The relay generates a 15- or 30-cycle event report in response
to faults or disturbances. Each report contains current and volt-
age information, relay element states, and input/output contact
information. If you question the relay response or your test
method, use the event report for more information. The
EVENT
command is available at the serial ports. See
Section 12: Standard Event Reports, Sag/Swell/Interruption
Report, and SER
.
SER
Command
The relay provides a Sequential Events Recorder (SER) event
report that time tags changes in relay element and input/output
contact states. The SER provides a convenient means to verify
the pickup/dropout of any element in the relay. The
SER
com-
mand is available at the serial ports. See
Event Reports, Sag/Swell/Interruption Report, and SER
TARGET
Command
Use the
TARGET
command to view the state of relay control
inputs, relay outputs, and relay elements individually during a
test. The
TARGET
command is available at the serial ports and
the front panel. See
Section 10: Serial Port Communications
Section 11: Front-Panel Interface
.
PULSE
Command
Use the
PULSE
command to test the contact output circuits.
The
PULSE
command is available at the serial ports and the
front panel.
Section 10: Serial Port Communications and Com-
.
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...