12.32
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Standard Event Reports, Sag/Swell/Interruption Report, and SER
Example Sequential Events Recorder (SER) Report
Example Sequential Events Recorder (SER) Report
The following example sequential events recorder (SER) report in
(from a Model 0351
x
0 relay) also corresponds to the example standard
15-cycle event report in
.
FEEDER 1 Date: 04/12/99 Time: 10:20:16.896
STATION A
FID=SEL-351-14-X300-VO-D990426 CID=2516
# DATE TIME ELEMENT STATE
19 04/12/99 08:30:33.222 Relay newly powered up
18 04/12/99 09:20:22.830 IN102 Asserted
17 04/12/99 09:27:58.364 LB4 Asserted
16 04/12/99 09:27:58.364 OUT102 Asserted
15 04/12/99 09:27:58.368 LB4 Deasserted
14 04/12/99 09:27:58.385 IN101 Asserted
13 04/12/99 09:27:58.385 OUT102 Deasserted
12 04/12/99 09:28:03.385 79LO Deasserted
11 04/12/99 09:28:31.717 51G Asserted
10 04/12/99 09:28:31.721 51P Asserted
9 04/12/99 09:28:31.729 50P1 Asserted
8 04/12/99 09:28:31.729 79CY Asserted
7 04/12/99 09:28:31.729 OUT101 Asserted
6 04/12/99 09:28:31.808 50P1 Deasserted
5 04/12/99 09:28:31.816 51G Deasserted
4 04/12/99 09:28:31.816 51P Deasserted
3 04/12/99 09:28:31.816 IN101 Deasserted
2 04/12/99 09:28:31.879 OUT101 Deasserted
1 04/12/99 09:28:36.874 OUT102 Asserted
Figure 12.7
Example Sequential Events Recorder (SER) Event Report
are explained in the following text,
numbered in correspondence to the
#
column. The boxed, numbered
comments in
also correspond to the
#
column numbers in
. The SER event report in
contains records of events
that occurred before and after the standard event report in
SER
Row No.
Explanation
19
Relay newly powered up.
18
Input
IN102
is asserted to enable reclosing.
Related setting:
79DTL = !IN102 + ...[=NOT(IN102) + ...]
17, 16
Local bit LB4 is operated from the front panel to assert close output contact
OUT102
to close the circuit breaker (see
Related settings:
CL = LB4 (LB4 operates as a manual close)
OUT102 = CLOSE
15
Local bit LB4 deasserts automatically the next 1/4 cycle—close signal is
latched in by close logic.
14, 13
Input
IN101
asserts, indicating that the circuit breaker closed. Close output
contact
OUT102
consequently deasserts.
Related setting: 52A = IN101
12
The relay leaves the Lockout State (79LO) and goes to the Reset State,
300 cycles after the circuit breaker closes.
Related setting: 79RSLD = 300.000 cycles
Time difference: 09:28:03.385–09:27:58.364 = 5.021 seconds
(= 300 cycles)
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...