Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Section 9
R.Instruction Manual
Setting the Relay
Overview
Change or view settings with the
SET
and
SHOWSET
serial port commands
and the front-panel
{SET}
pushbutton.
lists the serial port
SET
commands.
View settings with the respective serial port
SHOWSET
commands (
SHO
,
SHO L
,
SHO G
,
SHO R
,
SHO T
,
SHO P
.
In Some Applications,
Make Global Settings
(SET G) First
Make global settings (
Global Settings (Serial Port Command SET G and Front
) before making other relay settings for applications
that require delta-connected PTs, or applications requiring an external zero-
sequence voltage source to be connected to the relay. Changing global settings
PTCONN or VSCONN automatically resets many of the remaining relay
settings to default values. For example, any settings previously entered for the
group settings (
SET
;
SET 1
–
SET 6
), logic settings (
SET L
;
SET L 1
–
SET
L 6
), and report settings (
SET R
) will be lost and will need to be re-entered.
The relay will provide two confirmation prompts prior to accepting a change
to either PTCONN or VSCONN. See
Delta-Connected Voltages (Global
Setting PTCONN = DELTA) on page 2.13
and
(Global Setting VSCONN = 3V0) on page 2.14
.
Applications that use wye-connected PTs and have no external zero-sequence
voltage source connection do not require changes in the PTCONN and
VSCONN settings, so are not affected by the order of setting entry.
Table 9.1
Serial Port SET Commands
Command
Settings
Type
Description
Settings
Sheets
a
a
Located at the end of this section.
SET
n
Relay
Overcurrent and voltage elements,
reclosing relay, timers, etc., for
settings group
n
(
n
= 1, 2, 3, 4, 5, 6).
1–17
SET L
n
Logic
SEL
OGIC®
control equations
for settings group
n
(
n
= 1, 2, 3, 4, 5, 6).
18–23
SET G
Global
Battery and breaker monitors,
optoisolated input debounce timers,
synchrophasors, etc.
24–27
SET R
SER
Sequential Events Recorder
trigger conditions and Load Profile settings.
28–29
SET T
Text
Front-panel default display and local control text.
30–33
SET P
n
Port
Serial port settings for
Serial Port
n
(
n
= 1, 2, 3, or F).
34
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...