7.24
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Inputs, Outputs, Timers, and Other Control Logic
Multiple Setting Groups
Figure 7.22
Rotating Selector Switch Connected to Inputs IN101, IN102, and
IN103 for Active Setting Group Switching
The selector switch has multiple internal contacts arranged to assert inputs
IN101
,
IN102
, and
IN103
, dependent on the switch position. As shown in
, as the selector switch is moved from one position to another, a
different setting group is activated. The logic in
is implemented in
the SEL
OGIC
are made in each setting Group 1 through 6.
Selector Switch Starts Out in Position 3
.
If the selector switch is in position 3 in
, setting Group 3 is the
active setting group (Relay Word bit SG3 = logical 1). Inputs
IN101
and
IN102
are energized and
IN103
is de-energized:
SS3 =
!IN103 * IN102 * IN101
= NOT(IN103) * IN102 * IN101
= NOT(logical 0) * logical 1 * logical 1 = logical 1
To get from position 3 to position 5 on the selector switch, the switch passes
through position 4. The switch is only briefly in position 4:
SS4 =
IN103 * !IN102 * !IN101
= IN103 * NOT(IN102) * NOT(IN101)
= logical 1 * NOT(logical 0) * NOT(logical 0) = logical 1
but not long enough to be qualified by time setting TGR in order to change the
active setting group to setting Group 4. For such a rotating selector switch
application, qualifying time setting TGR is typically set at 180 to 300 cycles.
Table 7.7
SEL
OGIC
Control Equation Settings for Rotating Selector Switch
Active Setting Group Switching
SS1 = !IN103 * !IN102 * IN101
= NOT(IN103) * NOT(IN102) * IN101
SS2 = !IN103 * IN102 * !IN101
= NOT(IN103) * IN102 * NOT(IN101)
SS3 = !IN103 * IN102 * IN101
= NOT(IN103) * IN102 * IN101
SS4 = IN103 * !IN102 * !IN101
= IN103 * NOT(IN102) * NOT(IN101)
SS5 = IN103 * !IN102 * IN101
= IN103 * NOT(IN102) * IN101
SS6 = IN103 * IN102 * !IN101
= IN103 * IN102 * NOT(IN101)
SEL-351
IN102
(–)
IN101
IN103
Remote
1
2
3
4
5
6
(+)
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...