Date Code 20010625
Close and Reclose Logic
6-15
SEL-311L Instruction Manual
Reclosing Relay Timer Settings
Example open interval and reset timer settings are shown in Table 6.2.
Table 6.2: Reclosing Relay Timer Settings and Setting Ranges
Timer Setting
(range)
Setting
(in cycles)
Definition
79OI1 (0.00–999999 cyc)
30.00
open interval 1 time
79OI2 (0.00–999999 cyc)
600.00
open interval 2 time
79OI3 (0.00–999999 cyc)
0.00
open interval 3 time, shot 3 and shot
4 disabled
79OI4 (0.00–999999 cyc)
0.00
open interval 4 time
79RSD (0.00–999999 cyc)
1800.00
reset time from reclose cycle state
79RSLD (0.00–999999 cyc)
300.00
reset time from lockout state
79CLSD (OFF, 0.00–999999 cyc)
OFF
reclose supervise time limit
The operation of these timers is affected by SEL
OGIC
control equation settings discussed later in
this section. Also see the settings sheets at the end of
Section 9: Setting the Relay
.
Open Interval Timers
The reclose enable setting, E79, determines the number of open interval time settings that can be
set. For example, if setting E79 = 3, the first three open interval time settings in Table 6.2 are
made available for setting.
If an open interval time is set to zero, then that open interval time is not operable, and neither are
the open interval times that follow it.
In the example settings in Table 6.2, the open interval 3 time setting 79OI3 is the first open
interval time setting set equal to zero:
79OI3 =
0.00
cycles
Thus, open interval times 79OI3 and 79OI4 are not operable. In the example settings, both open
interval times 79OI3 and 79OI4 are set to zero. But if the settings were:
79OI3 =
0.00
cycles
79OI4
= 900.00 cycles (set to some value other than zero)
open interval time 79OI4 would still be inoperative, because a preceding open interval time is set
to zero (i.e., 79OI3 = 0.00).
If open interval 1 time setting, 79OI1, is set to zero (79OI1 = 0.00 cycles), no open interval
timing takes place, and the reclosing relay is defeated.
The open interval timers time consecutively; they do not have the same beginning time reference
point. In the above example settings, open interval 1 time setting, 79OI1, times first. If the
subsequent first reclosure is not successful, then open interval 2 time setting, 79OI2, starts
Содержание SEL-311L
Страница 6: ......
Страница 8: ......
Страница 26: ......
Страница 54: ......
Страница 144: ......
Страница 203: ...Date Code 20010625 Trip and Target Logic 5 27 SEL 311L Instruction Manual Figure 5 12 DCUB Logic ...
Страница 216: ......
Страница 252: ......
Страница 302: ......
Страница 338: ......
Страница 480: ......
Страница 484: ......
Страница 486: ......
Страница 502: ......
Страница 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Страница 552: ......
Страница 554: ......
Страница 574: ......
Страница 576: ......
Страница 596: ......
Страница 602: ......
Страница 628: ......
Страница 656: ......
Страница 662: ......
Страница 664: ......
Страница 688: ......
Страница 700: ......
Страница 716: ......
Страница 722: ......
Страница 734: ......