Date Code 20010625
Trip and Target Logic
5-11
SEL-311L Instruction Manual
Figure 5.5 and the following discussion describe the three-pole open (3PO) logic and the SOTF
logic.
Figure 5.5: Three-Pole Open Logic (Top) and Switch-Onto-Fault Logic (Bottom)
Three-Pole Open Logic
Three-pole open (3PO) logic is the top half of Figure 5.5. It is not affected by enable setting
ESOTF (see the settings sheets in
Section 9: Setting the Relay
).
The open circuit breaker condition is determined by load current (50L) and either one of:
v
Circuit breaker status (52A = logical 0), recommended
v
Positive-sequence voltage (|V1| < 27PO), not recommended when 87L protection is
enabled
Select OPO = 52 if 3PO is determined by circuit breaker status. Select OPO = 27 if 3PO is
determined by positive-sequence voltage and if 87L protection is not used.
Содержание SEL-311L
Страница 6: ......
Страница 8: ......
Страница 26: ......
Страница 54: ......
Страница 144: ......
Страница 203: ...Date Code 20010625 Trip and Target Logic 5 27 SEL 311L Instruction Manual Figure 5 12 DCUB Logic ...
Страница 216: ......
Страница 252: ......
Страница 302: ......
Страница 338: ......
Страница 480: ......
Страница 484: ......
Страница 486: ......
Страница 502: ......
Страница 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Страница 552: ......
Страница 554: ......
Страница 574: ......
Страница 576: ......
Страница 596: ......
Страница 602: ......
Страница 628: ......
Страница 656: ......
Страница 662: ......
Страница 664: ......
Страница 688: ......
Страница 700: ......
Страница 716: ......
Страница 722: ......
Страница 734: ......