8.13
Date Code 20060320
Instruction Manual
SEL-311C Relay
Breaker Monitor and Metering Functions
Breaker Monitor
Determination of
Relay-Initiated Trips
and Externally
Initiated Trips
BRE Command (Breaker Monitor Data)
. Note in the
BRE
command
response that the accumulated number of trips and accumulated interrupted
current are separated into two groups of data: that generated by
relay-
initiated trips
(Rly Trips) and that generated by
externally initiated trips
(Ext Trips). The categorization of these data is determined by the status of the
TRIP Relay Word bit when the SEL
OGIC
control equation breaker monitor
initiation setting BKMON operates.
and the accompanying explanation. If BKMON newly
asserts (logical 0 to logical 1 transition), the relay reads in the current values
(Phases A, B, and C). Now the decision has to be made: where is this current
and trip count information accumulated? Under relay-initiated trips or
externally initiated trips?
To make this determination, the status of the TRIP Relay Word bit is checked
at the instant BKMON newly asserts (TRIP is the logic output of
If TRIP is asserted (TRIP = logical 1), the current and trip count information
is accumulated under relay-initiated trips (Rly Trips). If TRIP is deasserted
(TRIP = logical 0), the current and trip count information is accumulated
under externally initiated trips (Ext Trips).
Regardless of whether the current and trip count information is accumulated
under relay-initiated trips or externally initiated trips, this same information is
routed to the breaker maintenance curve for continued breaker wear
integration (see
–
).
Setting Example
As discussed previously, the SEL
OGIC
control equation breaker monitor
initiation may be set:
BKMON =
TRIP
Thus, any new assertion of BKMON will be deemed a relay trip, and the
current and trip count information is accumulated under relay-initiated trips
(Rly Trips).
Additional Example
. Output contact
OUT101
is set to provide tripping:
OUT101 =
TRIP
Note that optoisolated input
IN106
monitors the trip bus. If the trip bus is
energized by output contact
OUT101
, an external control switch, or some other
external trip, then
IN106
is asserted.
Figure 8.8
Input IN106 Connected to Trip Bus for Breaker Monitor Initiation
TC
CS/T
(Control
Switch Trip)
Other
External
Trips
OUT101
= TRIP
TRIP
COIL
52A
IN106
Trip Bus
SEL-311C
(+)
(—)
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...