![Schweitzer Engineering Laboratories SEL-311B Скачать руководство пользователя страница 393](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-311b/sel-311b_instruction-manual_1216695393.webp)
Date Code 20011205
Standard Event Reports and SER
12-27
SEL-311B Instruction Manual
Figure 12.3 and Figure 12.4 look in detail at 1 cycle of B-phase current (channel IB) identified in
Figure 12.2. Figure 12.3 shows how the event report ac current column data relates to the actual
sampled waveform and RMS values. Figure 12.4 shows how the event report current column
data can be converted to phasor RMS values. Voltages are processed similarly.
Figure 12.3: Derivation of Event Report Current Values and RMS Current Values From
Sampled Current Waveform
In Figure 12.3, note that any two rows of current data from the event report in Figure 12.2,
1/4 cycle apart, can be used to calculate RMS current values.