11-8
Front-Panel Interface (Only on Models with LCD)
Date Code 20011205
SEL-311B Instruction Manual
If the breaker is closed, the reclosing relay reset timer times out (79RSLD = 300), the relay goes
to the reset state (front-panel LO LED extinguishes and RS LED illuminates), and the shot
counter returns to 0. The reclosing relay shot counter screen appears as:
SET RECLOSURES=2
RECLOSE COUNT =0
Local Control
Use local control to enable/disable schemes, trip/close breakers, etc., via the front panel.
In more specific terms, local control asserts (sets to logical 1) or deasserts (sets to logical 0) what
are called local bits LB1 through LB16. These local bits are available as Relay Word bits and
are used in SEL
OGIC
®
control equations (see Rows 5 and 6 in Table 9.3 and Table 9.4).
Local control can emulate the following switch types in Figure 11.5 through Figure 11.7.
Figure 11.5: Local Control Switch Configured as an ON/OFF Switch
Figure 11.6: Local Control Switch Configured as an OFF/MOMENTARY Switch
Figure 11.7: Local Control Switch Configured as an ON/OFF/MOMENTARY Switch
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......