Date Code 20011205
Close and Reclose Logic
6-13
SEL-311B Instruction Manual
The reclose enable setting, E79, has setting choices N, 1, 2, 3, and 4. Setting E79 = N defeats the
reclosing relay. Setting choices 1 through 4 are the number of desired automatic reclosures (see
Open Interval Timers
that follows in this subsection).
Reclosing Relay States and General Operation
Figure 6.5 explains in general the different states of the reclosing relay and its operation.
Figure 6.5: Reclosing Relay States and General Operation
Table 6.1: Relay Word Bit and Front-Panel Correspondence to Reclosing Relay States
Reclosing Relay State
Corresponding
Relay Word Bit
Corresponding
Front-Panel LED
Reset 79RS RS
Cycle 79RCY CY
Lockout 79LO LO
The reclosing relay is in one (and only one) of these states (listed in Table 6.1) at any time.
When in reset or lockout, the corresponding Relay Word bit asserts to logical 1, and the LED
illuminates. Automatic reclosing only takes place when the relay is in the Reclose Cycle State.
Содержание SEL-311B
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 26: ......
Страница 122: ......
Страница 124: ......
Страница 138: ......
Страница 168: ......
Страница 172: ......
Страница 254: ......
Страница 282: ......
Страница 306: ......
Страница 348: ......
Страница 364: ......
Страница 366: ......
Страница 448: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 482: ......
Страница 494: ......
Страница 500: ......
Страница 522: ......
Страница 526: ......
Страница 528: ......
Страница 534: ......
Страница 536: ......
Страница 550: ......
Страница 570: ......
Страница 586: ......
Страница 600: ......