Date Code 20011205
Loss-of-Potential, CCVT Transient Detection,
4-9
Load-Encroachment, and Directional Element Logic
SEL-311A Instruction Manual
Figure 4.5: General Logic Flow of Directional Control for Ground Distance and Residual
Ground Overcurrent Elements
Figure 4.5 gives an overview of how these directional elements are enabled and routed to control
the ground distance and residual ground overcurrent elements.
Note in Figure 4.5 that setting ORDER enables the directional elements. Setting ORDER can be
set with any combination of Q, V, and I. They have the following correspondence to the
directional elements:
Q Negative-sequence voltage-polarized directional element
V Zero-sequence voltage-polarized directional element
I Channel IP current-polarized directional element
The order in which these directional elements are listed in setting ORDER determines the priority
in which they operate to provide Best Choice Ground Directional
™
logic control. See discussion
on setting ORDER in the following subsection
Directional Control Settings
.
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......