4-8
Loss-of-Potential, CCVT Transient Detection,
Date Code 20011205
Load-Encroachment, and Directional Element Logic
SEL-311A Instruction Manual
Use SEL-321 Relay Application Guide for the SEL-311A Relay
The load-encroachment logic and settings in the SEL-311A Relay are the same as those in the
SEL-321 Relay. Refer to
SEL-321 Relay Load-Encroachment
for applying the load-encroachment logic in the SEL-311A Relay.
D
IRECTIONAL
C
ONTROL FOR
G
ROUND
D
ISTANCE AND
R
ESIDUAL
G
ROUND
O
VERCURRENT
E
LEMENTS
Setting E32 configures directional control for distance and overcurrent elements. Setting E32 and
other directional control settings are described in the following subsection
Directional Control
Settings
.
Three directional elements are available to control the ground distance and residual ground
overcurrent elements. These three directional elements are:
·
Negative-sequence voltage-polarized directional element
·
Zero-sequence voltage-polarized directional element
·
Channel IP current-polarized directional element
Содержание SEL-311A
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 24: ......
Страница 40: ......
Страница 66: ......
Страница 96: ......
Страница 98: ......
Страница 112: ......
Страница 114: ......
Страница 122: ......
Страница 170: ......
Страница 202: ......
Страница 204: ......
Страница 246: ......
Страница 248: ......
Страница 286: ......
Страница 290: ......
Страница 304: ......
Страница 306: ......
Страница 334: ......
Страница 384: ......
Страница 386: ......
Страница 394: ......
Страница 398: ......
Страница 402: ......
Страница 404: ......
Страница 410: ......
Страница 412: ......
Страница 426: ......
Страница 444: ......
Страница 460: ......
Страница 474: ......