Date Code 20011205
Breaker Monitor and Metering Functions
8-25
SEL-311A Instruction Manual
GDEMP
=
1.0
51GP =
1.50
50G1P
=
2.30
51GTC = !GDEM + GDEM * 50G2
Refer to Figure 8.13, Figure 8.14, and Figure 3.15.
Figure 8.14: Raise Pickup of Residual Ground Time-Overcurrent Element for Unbalance
Current
Residual Ground Demand Current Below Pickup GDEMP
When unbalance current I
G
is low, unbalance demand current I
G(DEM)
is below corresponding
demand pickup GDEMP = 1.00 A secondary, and Relay Word bit GDEM is deasserted to
logical 0. This results in SEL
OGIC
control equation torque control setting 51GTC being in the
state:
51GTC = !GDEM + GDEM * 50G1 = NOT(GDEM) + GDEM * 50G1
= NOT(logical 0) + (logical 0) * 50G1 = logical 1
Thus, the residual ground time-overcurrent element 51GT operates on its standard pickup:
51GP
= 1.50 A secondary