SST Extreme X & SST Extreme S MODULATING I&O Manual
RD: JAN 2021
RL: 1A
13. FIELD CONVERSION OF FUEL GAS: SST
-
MX & SST
-
MS MODULATING BURNERS
Tube Heater Burners are factory produced and supplied to operate on natural gas.
A field conversion kit is available from the manufacturer and must be used to convert from natural
gas to propane gas, or vice versa. Each kit contains the required parts and specific instructions to
make the gas conversion. Refer to the table below for kit part numbers.
NOTE: All Kits include a Gas Orifice*, and Valve Conversion Kit with Pressure Regulator
Spring and Cap, and instructions to convert the gas valve and install the kit.
* Gas Orifice in the Field Conversion Kit:
◼
USA: 0 to 2,000 ft
◼
Canada: 0 to 4,500 ft
◼
Refer to
“
High Altitude
”
section for altitudes higher than listed above
Gas Conversion Kits
-
Order by Part Number
Input Rate
(BTUH)
Conversion Kit
NG to PROPANE
80,000
JS
-
0554
-
AL
115,000
JS
-
0554
-
CL
155,000
JS
-
0554
-
EL
205,000
JS
-
0554
-
GL
260,000
JS
-
0554
-
JL
TABLE
6
–
GAS CONVERSON KITS