L-01394-4-05 

2.1   Use at low temperatures 

 

The safety of the light fitting is warranted between -30°C up to +40°C/+55°C. 
At temperatures below 0 °C, it must be taken into account that the emergency battery will take longer 
to charge and the operational life of the emergency lighting mode will be reduced. Testing the duration 
of the battery life in lower ambient temperatures can therefore lead to a misleading result. 
The battery life test should be repeated manually at a more appropriate time (please refer to the 
section about operational life testing in Chapter 2.2).  

 

2.2   Automatic test of the emergency light unit 

 

The functionality of the light fitting and the operational life in emergency lighting mode is tested 
automatically by the emergency light unit at specified intervals. A blinking green light is emitted by the 
signal LED while the test is being carried out. 

 

Functionality test 
Functionality tests are carried out at 7 day intervals and last one minute. 
The first test of functionality is carried out one hour after the light fitting has been setup. Before this can 
happen, it is necessary to separate the emergency light unit built into the light fitting from the mains 
power supply before switching on the power, and the emergency battery must have been charged 
continuously for one hour. 

 

Operational life test 
During the operational life test, the emergency light unit checks whether the capacity of the emergency 
battery is sufficient for the indicated nominal operating time should the emergency light being required. 

 

For the operational life test to be carried out, the emergency battery must be fully charged and 
connected. For special versions with the option to deactivate the emergency light function, the remote 
cutoff switch must also be closed. 

 

Automatic operational life tests: 
The first operational life test carried out automatically by the emergency light unit takes place at 
random within a period of 5 to 28 days after the light fitting has been setup. All further automatic 
operational life tests are then carried out at 52 week intervals, so long as the energy supply to the 
emergency light unit was not interrupted during this period.  
A complete interruption of the energy supply to the emergency light unit occurs when the outage of the 
power supply exceeds the specified nominal operating time for the emergency light.  
Reconnecting the power supply to the emergency light unit after a complete interruption will lead to a 
new setup procedure of the emergency light with a subsequent operational life test between 5 and 28 
days later. 
Should a fault in the battery capacity be indicated before a complete interruption of the power supply to 
the emergency light unit, a operational life test will be carried out within 24 hours of reconnection to the 
power supply. 
If the prerequisites stated above for carrying out an automatic operational life test are not satisfied, the 
test will be deferred until these requirements are fulfilled.  
Automatic operational life tests that could not be completed successfully will be repeated once after 60 
hours, subject to the same prerequisites stated above. 

 

Manual operational life tests: 
Operational life tests can be triggered manually in 2 ways. Models with battery box can be triggered 
manually in 3 ways: 

 

1. By switching the power supply off and on at the L1 terminal. 
2. By switching the supply on and off at the L1` terminal. 

 

Switch the power supply at the L1 terminal resp. the supply at L1' terminal off and on again 5 times. 
Leave at least 2 seconds between each switch.

 

 

In both cases, the sequence of switches must be completed within 60 seconds. 
Under the above mentioned preconditions, after a correctly performed switching sequence at L1' 
terminal, an operational life test is immediately initiated.  
If the switching sequence is correctly carried out on L1 terminal, an operational life test is initiated after 

Содержание nD867.12L Series

Страница 1: ...ends on the observance of all safety standards Exact knowledge about all applicable regulations and standards is mandatory for installation maintenance and repair of explosion proof equipment especial...

Страница 2: ...thermically or electrically or if the light fitting will be subject to any kind of vibrations it is highly recommended to consult the Adolf Schuch GmbH before starting the installation Every structur...

Страница 3: ...tected against mechanical and electrostatic attacks whenever the light fitting is open For this reason the LED must not be touched either Due to harmful gases and other corrosive substances e g ammoni...

Страница 4: ...out automatically by the emergency light unit takes place at random within a period of 5 to 28 days after the light fitting has been setup All further automatic operational life tests are then carrie...

Страница 5: ...val until the next regular operational life test is unaffected During the functionality and operational life tests the light fitting will switch on even if it was previously switched off 2 3 Ascertain...

Страница 6: ...5 Instructions for special versions with remote cutoff switch Special versions of these lighting fixtures are equipped to be connected to a remote cutoff switch Through a remote cutoff switch isolated...

Страница 7: ...us areas of zones 2 and 22 Explosion protection o II 3 G Ex ec IIC T4 Gc Version without battery box o II 3 G Ex db ec IIC T4 Gc Version with battery box o II 3 D Ex tc IIIC T80 C Dc Certification SH...

Страница 8: ...uctor 0 75 1 0 mm 9 mm conductor 1 5 2 5 mm See information label on the front page when having special versions Locking Clamp lockings to be opened by hand as well as one safety closure at each side...

Страница 9: ...fitting in an explosive dust atmosphere is depending on the properties of the surrounding dust Please ensure that there will be an adequate difference between the maximum surface temperature of the f...

Страница 10: ...ntries which are not used must be closed with the enclosed closure plug see Chapter 3 Technical Data An inlaid dust protective disc if existing must be removed before The conductors must not be damage...

Страница 11: ...emergency battery Version with battery box Open the battery box by loosening the locking screws and flip open the lid Remove the protective cap from the connector of the battery cable Attach the conn...

Страница 12: ...ect to any tension whatsoever the bare conductor is fully inserted into the terminal and that no cable insulation is clamped the light fitting is closed correctly all gaskets are effective the light f...

Страница 13: ...soft fibrous free cloth Pay attention to the following in case of application of this light fitting in dusty atmospheres Dust deposits have got thermal insulation characteristic features It is necess...

Страница 14: ...to the presence of a new battery Open and close the lid of the battery box twice within a 60 second period Opening and closing the case must occur within 10 seconds of each other If this procedure is...

Страница 15: ...though the connection to the battery still exists In this case the emergency battery is to be removed as described in Section 6 3 and to be charged separately from the light fitting With a 6V charging...

Страница 16: ...16 L 01394 4 05 The test certificates are ready to be loaded down from our homepage www schuch de or we shall send it on request Misprints modifications and errors are excepted...

Отзывы: