nD867. 12L .. / . / .  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

The safety of people and equipment in hazardous areas depends on the 
observance of all safety standards. Exact knowledge about all applicable 
regulations and standards is mandatory for installation maintenance and 
repair of explosion proof equipment, especially 

 

 the determinations of IEC/EN 60079-14 and IEC/EN 60079-17 for 

maintenance of explosion-proof appliances  

 

 the generally accepted rules of the technical side 

 

 the national rules for prevention of accidents and for safety standards  

 

 the safety instructions of these operating instructions  

 

 the characteristic data on the type plate and the instruction plates 

Содержание nD867.12L Series

Страница 1: ...ends on the observance of all safety standards Exact knowledge about all applicable regulations and standards is mandatory for installation maintenance and repair of explosion proof equipment especial...

Страница 2: ...thermically or electrically or if the light fitting will be subject to any kind of vibrations it is highly recommended to consult the Adolf Schuch GmbH before starting the installation Every structur...

Страница 3: ...tected against mechanical and electrostatic attacks whenever the light fitting is open For this reason the LED must not be touched either Due to harmful gases and other corrosive substances e g ammoni...

Страница 4: ...out automatically by the emergency light unit takes place at random within a period of 5 to 28 days after the light fitting has been setup All further automatic operational life tests are then carrie...

Страница 5: ...val until the next regular operational life test is unaffected During the functionality and operational life tests the light fitting will switch on even if it was previously switched off 2 3 Ascertain...

Страница 6: ...5 Instructions for special versions with remote cutoff switch Special versions of these lighting fixtures are equipped to be connected to a remote cutoff switch Through a remote cutoff switch isolated...

Страница 7: ...us areas of zones 2 and 22 Explosion protection o II 3 G Ex ec IIC T4 Gc Version without battery box o II 3 G Ex db ec IIC T4 Gc Version with battery box o II 3 D Ex tc IIIC T80 C Dc Certification SH...

Страница 8: ...uctor 0 75 1 0 mm 9 mm conductor 1 5 2 5 mm See information label on the front page when having special versions Locking Clamp lockings to be opened by hand as well as one safety closure at each side...

Страница 9: ...fitting in an explosive dust atmosphere is depending on the properties of the surrounding dust Please ensure that there will be an adequate difference between the maximum surface temperature of the f...

Страница 10: ...ntries which are not used must be closed with the enclosed closure plug see Chapter 3 Technical Data An inlaid dust protective disc if existing must be removed before The conductors must not be damage...

Страница 11: ...emergency battery Version with battery box Open the battery box by loosening the locking screws and flip open the lid Remove the protective cap from the connector of the battery cable Attach the conn...

Страница 12: ...ect to any tension whatsoever the bare conductor is fully inserted into the terminal and that no cable insulation is clamped the light fitting is closed correctly all gaskets are effective the light f...

Страница 13: ...soft fibrous free cloth Pay attention to the following in case of application of this light fitting in dusty atmospheres Dust deposits have got thermal insulation characteristic features It is necess...

Страница 14: ...to the presence of a new battery Open and close the lid of the battery box twice within a 60 second period Opening and closing the case must occur within 10 seconds of each other If this procedure is...

Страница 15: ...though the connection to the battery still exists In this case the emergency battery is to be removed as described in Section 6 3 and to be charged separately from the light fitting With a 6V charging...

Страница 16: ...16 L 01394 4 05 The test certificates are ready to be loaded down from our homepage www schuch de or we shall send it on request Misprints modifications and errors are excepted...

Отзывы: