Representation of measuring range
The measuring range of the corresponding measuring value is mapped
in a linear way to the mode-specific signaling range of the associated
analog output.
For flow velocity measurement, it ranges from zero up to the selectable
end of the measuring range w
N,max
(see Table 7).
Voltage mode (U)
Current mode (I)
𝑤
𝑁
=
𝑤
𝑁,𝑚𝑎𝑥
10 𝑉
∙ 𝑈
𝑂𝑢𝑡,𝑤
𝑁
𝑤
𝑁
=
𝑤
𝑁,𝑚𝑎𝑥
16 𝑚𝐴
∙ (𝐼
𝑂𝑢𝑡,𝑤
𝑁
− 4 𝑚𝐴)
Table 7 Representation specification for flow velocity measurement
The measuring range of the medium temperature starts at the selected
measuring range T
Min
and ends at 120 °C (see Table 8).
Voltage mode (U)
Current mode (I)
𝑇
𝑀
=
120 °𝐶 − 𝑇
𝑀𝑖𝑛
10 𝑉
∙ 𝑈
𝑂𝑢𝑡,𝑇
𝑀
+ 𝑇
𝑀𝑖𝑛
𝑇
𝑀
=
120 °𝐶 − 𝑇
𝑀𝑖𝑛
16 𝑚𝐴
∙ (𝐼
𝑂𝑢𝑡,𝑇
𝑀
− 4 𝑚𝐴) + 𝑇
𝑀𝑖𝑛
Table 8 Representation specification for measurement of medium temperature