Operating instructions
Hinge safety switch
TV.S 335
TV.S 355
EN
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages
resulting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary
repairs, conversions and modifications to the device are strictly
forbidden; the manufacturer shall accept no liability for damages
resulting from such invasive work, arbitrary repairs, conversions and/or
modifications to the device.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
TV
➀
S 3
➁
5-
➂
Z-
➃
No. Option
Description
➀
8
Shaft bore ø 8 mm
10
Shaft bore ø 10 mm
➁
3
slim design
5
large design
➂
02
2 NC contacts
03
3 NC contacts
11
1 NO contacts / 1 NC contacts
12
1 NO contacts / 2 NC contacts
➃
cable entry M20
NPT
Cable entry NPT 1/2"
ST
M12 connector (A coding)
2310
M12 connector (B coding)
Only if the information described in this operating instructions
manual are realised correctly, the safety function and
therefore the compliance with the Machinery Directive is
maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specifications apply accordingly, provided that they correspond to
the standard version.
2.3 Destination and use
The hinge safety switches (Type 1 according to ISO 14119) are suitable
for hinged guards, which need to be closed in order to provide for the
necessary operational safety.
The user must evaluate and design the safety chain in
accordance with the relevant standards and the required
safety level.
The entire concept of the control system, in which the safety
component is integrated, must be validated to the relevant
standards.
2.4 Technical data
Standards:
IEC 60947-5-1; BG-GS-ET-15
Design:
EN 50041
Enclosure:
light-alloy diecast, paint finish
Protection class:
IP67
Contact material:
Silver
Contact type:
change-over contact with double break, type Zb or
1 NC or 2 NC contacts,
with galvanically separated contact bridges
Switching system:
A IEC 60947-5-1; slow action,
NC contact with positive break
Connection:
screw terminals
Cable section (rigid / flexible):
min. 0.75 mm²,
max. 2.5 mm²
(including conductor ferrules)
Cable entry:
TV.S 335: 1 x M20
TV.S 355: 3 x M20
Rated impulse withstand voltage U
imp
:
6 kV;
- Versions TV.S 355-03 and ...-12:
4 kV
- Connector:
0.8 kV
Rated insulation voltage U
i
:
500 V;
- Versions TV.S 355-03 and ...-12:
250 V
- Connector:
50 V
Thermal test current I
the
:
10 A
Utilisation category:
AC-15, DC-13
Rated operating current/voltage I
e
/U
e
:
4 A / 230 VAC,
4 A / 24 VDC
- connector:
50 V
Required short-circuit current:
1000 A
Max. fuse rating:
6 A gG D-fuse
Ambient temperature:
−25 °C … +70 °C
Mechanical life:
1 million operations
Max. switching frequency:
1000/h
Shaft bore:
ø 8 mm / 10 mm
Positive break angle:
7°
Positive break torque:
0.6 Nm
2.5 Safety classification
Standards:
ISO 13849-1
Envisaged structure:
- Basically:
applicable up to Cat. 1 / PL c
- With 2-channel usage and
fault exclusion mechanism*:
applicable up to Cat. 3 / PL d
with suitable logic unit
B
10D
NC contact:
20,000,000
B
10d
NO contact at 10% ohmic contact load:
1,000,000
Service life:
20 years
* If a fault exclusion to the 1-channel mechanics is authorised.
MTTF
B
d x
x
h
s/h
3600
D
10D
op
op
op
n
0,1 x n
op
t
cycle
(Determined values can vary depending on the application-specific
parameters h
op
, d
op
and t
cycle
as well as the load.)
If multiple safety components are wired in series, the Performance
Level to ISO 13849-1 will be reduced due to the restricted error
detection under certain circumstances.