schmersal SRB 301LC/B-R Скачать руководство пользователя страница 5

5

SRB 301LC/B

SRB 301LC/B-R

Operating instructions

Safety-monitoring module

EN

The connection of magnetic safety switches to the  

SRB 301LC/B and SRB 301LC/B-R safety-monitoring  

module is only admitted when the requirements of the 

standard EN 60947-5-3:2005 are observed. 

As the technical data are regarded, the following minimum 

requirements must be met:

– switching capacity: min. 240 mW

– switching voltage: min. 24 VDC

– switching current: min. 10 mA

For example, the following safety sensors meet the 

requirements:

– BNS 33-02z-2187, BNS 33-02zG-2187

– BNS 260-02z, BNS 260-02zG

– BNS 260-02-01z, BNS 260-02-01zG

When sensors with LED are wired in the control circuit 

(protective circuit), the following rated operating voltage  

must be observed and respected:

–  24 VDC with a max. tolerance of –5 %/+ 20 %

–  24 VAC with a max. tolerance of –5 %/+ 10 %

Otherwise availability problems could occur, especially in 

series-wired sensors, where a voltage drop in the control 

circuit is triggered by LED's for instance.

Dual-channel control of a safety-related (microprocessor-based) 

safety guards with p-type transistor outputs e.g. AOPD's to  

IEC 61496-1 (Fig. 10)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the monitoring circuits are usually detected 

by the safety guards. The safety-monitoring module therefore is not 

equipped with a cross-wire short detection.

•  If cross-wire shorts in the control circuits are detected by the safety 

guard: Control category 4 – PL e to ISO 13849-1 possible.

S12 S22

S11

S11

S22

S12

S11

S11

S12 S22

+24V

+24V

Fig. 8

Fig. 9

Fig. 10

8.4  Actuator configuration

Single-channel control with feedback circuit (Fig. 11)

•  Suitable for increase in capacity or number of contacts by means  

of contactors or relays with positive-guided contacts.

•  

S

 = feedback circuit: If the feedback circuit is not required,  

establish a bridge.

Dual-channel control with feedback circuit (Fig. 12)

•  Suitable for increase in capacity or number of contacts by means  

of contactors or relays with positive-guided contacts.

•  

S

 = feedback circuit: If the feedback circuit is not required,  

establish a bridge.

X1

X2

13

14

K

A

K

A

S

N

L1

K

A

X1

X2

13

14

K

A

K

A

S

N

L1

K

B

K

B

K

B

K

A

Fig. 11

Fig. 12