schmersal EX-BNS 33 2187 Series Скачать руководство пользователя страница 4

4

Operating instructions

Safety sensor

EX-BNS 33-…-2187

EN

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition.

The safety sensors must be wired in accordance with the wire colours 

or the pin configuration.

4.2  Contact variants

The contact position shows the actuated sensor function when the 

safety guard is closed.  If the safety sensor is equipped with a LED,  

the LED will be illuminated when the guard is open.

Safety contacts:

02Z: S11-S12 and S21-S22

12Z: S21-S22 and S31-S32

Signalling contact:

12Z: S13-S14

EX-BNS 33-12Z(G)-2187-3G/D

EX-BNS 33-02Z(G)-2187-3G/D

GY 13

GN 21

WH 31

14 PK

22 YE

32 BN

BK 11

WH 21

12 BU

22 BN

4.3  Connection

For safety-monitoring modules with two NC inputs, the wires of the  

EX-BNS 33-12Z-2187-3G/D safety sensor must be wired as follows:

NC contacts:

WH (21) und BN (22)

at the "NC input" of the  

safety-monitoring module 

NC contacts:

GN (31) und YE (32)

at the "NC input" of the  

safety-monitoring module

NO contacts:

GY (13) und PK (14)

can be used for 

signalling purposes.

Information for the selection of suitable safety-monitoring 

modules can be found in the Schmersal catalogues or in 

the online catalogue on the Internet: www.schmersal.net.

Connecting multiple safety sensors to one suitable safety-monitoring 

module is technically possible. To connect multiple safety sensors 

(check if authorised!), their NO contacts are wired in parallel and their 

NC contacts in series.  The Protect-IE-11 or PROTECT-PE-11 (-AN) 

input expander module can be used to connect up to 4 safety sensors 

with NC/NO contacts.

When connecting the EX-BNS-33-12Z-2187-3G/D safety sensors to the 

AES 1102/1112/7112 safety-monitoring module, the connecting cables 

of the S14/S22/S32 of the EX-BNS must be wired to the terminals with 

the same label of the AES. The S13/S21/S31 connecting cables must 

be wired together to the C terminal of the AES (refer to AES operating 

instructions manual).

Connecting more than two magnetic safety sensors EX-BNS 

33-12Z-2187-3G/D to the safety monitoring modules AES 

1102/1112/7112 is not possible.

If safety sensors with LED's are used, the light intensity of the LED's 

will decrease as the number of open safety guards increases. Safety 

sensors equipped with LED's shall not be wired in series, except for 

the Protect-IE input expander module. As a result of this, the luminosity 

of the LED's would considerably decrease and the voltage could drop 

below the minimum input voltage of the downstream safety-monitoring 

module. 

In case of series-wiring at SRB max. 1 sensor with LED indication for U

N

.

Inductive loads (e.g. contactors, relays, etc.) are to be suppressed 

by means of a suitable circuit. If the EX-BNS 33 with LED is used in 

conjunction with an inappropriate AES safety-monitoring module, the 

energy restriction for LED versions (24 V/10 mA) must be ensured by 

the user.

5.  Set-up and maintenance

5.1  Functional testing

The safety function of the safety components must be tested.  

The following conditions must be previously checked and met:

1. The installation is executed according to the instructions

2. The connection is executed correctly

3. The safety component is not damaged

4.  The system is free of dirt and soiling (in particular metal chips)

5.  Check cable entry and connections in a de-energised condition

5.2  Maintenance

In the case of correct installation and adequate use, the safety sensor 

features maintenance-free functionality. A regular visual inspection and 

functional test, including the following steps, is recommended:

• Check the fitting of the sensor and the actuator

• Remove possible metal chips

• Check the cable for damage.

Adequate measures must be taken to ensure protection 

against tampering either to prevent tampering of the safety 

guard, for instance by means of replacement actuators.

Damaged or defective components must be replaced.

6.  Disassembly and disposal

6.1  Disassembly

The safety switchgear must be disassembled in a de-energised 

condition only.

6.2  Disposal

The safety switchgear must be disposed of in an appropriate manner  

in accordance with the national prescriptions and legislations.

Отзывы: