schmersal EX-AZM 415 Скачать руководство пользователя страница 2

2

Operating instructions

Solenoid interlock

EX-AZM 415

EN

1.6  Warning about misuse

In case of improper use or manipulation of the safety 

switchgear, personal hazards or damages to machinery 

or plant components cannot be excluded. The relevant 

requirements of the standard ISO 14119 must be observed.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

EX-AZM 415-

ZPK

-24VAC/DC-

-3D

No. Option

Description

11 / 11

2 NC contact / 2 NO contact

02 / 11

3 NC contact / 1 NO contact

02 / 20

2 NC contact / 2 NO contact

02 / 02

4 NC contacts

Power to unlock

A

Power to lock

1637

Gold-plated contacts

Only if the information described in this operating instructions 

manual are realised correctly, the safety function and 

therefore the compliance with the Machinery Directive and 

the Explosion Protection Directive is maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Purpose

The solenoid interlock has been designed to prevent in conjunction 

with the control part of a machine, movable safety guards from being 

opened before hazardous conditions have been eliminated.  The 

components can be used in explosion-endangered areas of Zone 22 

equipment category 3D. The installation and maintenance requirements 

to the standard series EN 60079 must be met.

Conditions for safe operation

Due to the specific impact energy, the components must be fitted 

with a protection against mechanical stresses. The specific ambient 

temperature range must be observed.  The user must provide for a 

protection against the permanent influence of UV rays.

Solenoid interlocks with power to lock principle may only 

be used in special cases after a thorough evaluation of 

the risk of accident, since the safety guard can be opened 

immediately on failure of the power supply or upon activation 

of the main switch.

The safety switchgears are classified according to ISO 14119 

as type 2 interlocking devices.

The user must evaluate and design the safety chain in 

accordance with the relevant standards and the required safety 

level.

The entire concept of the control system, in which the safety 

component is integrated, must be validated to the relevant 

standards. 

2.4  Technical data

Equipment category: 

L

 II 3D

Ex protection:

 

Ex tc IIIC T90°C Dc X

Standards:

 

IEC 60947-5-1, EN 60079-0,  

EN 60079-31, BG-GS-ET-19

Enclosure: 

light-alloy die-cast, enamel finish

Max. impact energy:

 

4 J

Actuating speed:

 

max. 1 m/s

Actuator: 

zinc-plated brass / aluminium

Protection class: 

IP67 to IEC 60529

Contact material:

 Silver

Coding level according to ISO 14119: 

low

Contact type:

 

Change-over with double break Zb,  

galvanically separated contact bridges

Switching system:

 

A

 IEC 60947-5-1; slow action,  

NC contact with positive break

Connection:

 

screw terminals

Cable section:

 2.5 mm² (including conductor ferrules)

Rated impulse withstand voltage U

imp

:

 

4 kV

Rated insulation voltage U

i

:

 

250 V

Thermal test current I

the

:

 

6 A

Utilisation category: 

AC-15

Rated operating current I

e

:

 

4 A / 230 VAC

Rated operating voltage U

e

:

 

4 A / 230 VAC

Max. fuse rating:

 

6 A gG D-fuse

Required short-circuit current: 

1000 A

Positive break travel: 

5 mm

Positive break force: 

min. 15 N  

(depending on the setting of the ball latch)

Rated control voltage U

s

:

 

24 VAC / DC

Magnet:

 

100% ED

Power consumption: 

max. 10 W

Ambient temperature:

 

–10 °C … +50 °C

Mechanical life:

 

max. 1 million operations

Holding force F

max

:

 

3500 N

Latching force: 

80 - 400 N (adjustable)

Tightening torque:

 

Cover screws: min. 0.6 Nm; 

Bottom cover screws: min. 0.7 Nm; 

Cable gland: min. 8 Nm; 

Blocking screws: min. 8 Nm

Cable glands:

 

L

 II 2GD

Cable cross-section:

 

min. Ø 7 mm; max. Ø 12 mm

2.5  Safety classification

Standards:

 

ISO 13849-1

Envisaged structure: 

 

- Basically:

 

applicable up to Cat. 1 / PL c 

-  With 2-channel usage and  

 

fault exclusion mechanism*:

 

applicable up to Cat. 3 / PL d  

with suitable logic unit

B

10D

 NC contact:

 2,000,000

B

10D

 NO contact at 10% ohmic contact load:

 1,000,000

Service life:

 

20 years

* If a fault exclusion to the 1-channel mechanics is authorised.

MTTF

B

d x

x

h

s/h

3600

D

10D

op

op

op

n

0,1 x n

op

t

cycle

(Specifications can vary depending on the application-specific 

parameters h

op

, d

op

, t

cycle

 as well as the load.)

If multiple safety components are wired in series, the Performance 

Level to ISO 13849-1 will be reduced due to the restricted error 

detection under certain circumstances.