schmersal CSS 34 Скачать руководство пользователя страница 5

5

CSS 34

Operating instructions

Safety sensor

EN

Actuation from side

The side allows for a maximum height misalignment (X) of sensor 

and actuator of 36 mm (e.g. mounting tolerance or due to guard door 

sagging). Increased misalignment, max. 53 mm, possible when the 

CST 34-S-2 actuator is used. The axial misalignment (Y) is max. ± 10 

mm.

Maximum misalignment from front

Z

Actuation from front

The front face allows for an axial misalignment 

(Z) of max. ± 8 mm.

3.5  Adjustment

The distance between the sensor and the actuator must be set to < S

ao

.  

If variations in the clearance between the sensor and the actuator is 

detected (e.g. sagging of a safety guard), this distance must be reduced 

by 4 mm. The yellow LEDs and the diagnostic output indicate the 

different ranges.

Recommended Adjustment

Align the safety sensor and actuator at a distance of 0.5 x s

ao

.

The correct functionality of both safety channels must be checked by 

means of the connected safety-monitoring module.

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by  

authorised personnel in a de-energised condition.

The power supply for the safety sensors must provide protection 

against permanent over-voltage. Under fault conditions, the voltage 

must not exceed 60 V. supply units according to IEC 60204-1 is 

recommended. 

The safety outputs can be integrated into the safety circuit of the control 

system. For applications of PL e / control category 4 to ISO 13849-1, 

the safety outputs of the safety sensor or sensor of the chain must be 

wired to a safety monitoring module of the same control category .

Requirements for the connected safety-monitoring module

•  Dual-channel safety input, suitable for p-type safety sensors with NO 

function. 

•  Digital inputs to EN 61131-2, Table "Standard operating ranges for 

digital inputs (current sinking)"

The safety sensors cyclically switch off the output to test them. The 

switch-off times of max. 500 μs must be tolerated by the evaluating 

device. Short-circuit recognition by the evaluation is not necessary. 

Note on the total length of a safety sensor chain, refer to paragraph 

"Series-wiring". The maximum load current of 250 mA per safety 

channel must be observed. Contactors with higher load currents must 

be controlled by intermediate control relays.

Information for the selection of suitable safety-monitoring 

modules can be found in the Schmersal catalogues or in the 

online catalogue on the Internet: www.schmersal.net.

The self-monitoring safety sensors of the CSS 34F0 or CSS 34F1 

series can replace the safety-monitoring module. Therefore, they can 

only be used as the first sensor of a series-wired sensor chain. (refer to 

operating instructions CSS 34F0 / CSS 34F1).

If the safety sensor is connected to electronic safety-

monitoring modules, we recommend that you set a 

discrepancy time of 100 ms.  The safety inputs of the safety-

monitoring module must be able blanking a test impulse of 

approx. 1 ms. The safety-monitoring module does not need to 

have a cross-wire short monitoring function, if necessary, the 

cross-wire short monitoring function must be disabled.

4.2  Series-wiring

Series-wiring can be set up. The number of devices is limited for safety 

reasons. Series-wiring of CSS 34-…-SD with serial diagnostics is 

possible for up to 31 devices. A 200 m long sensor chain can be set up. 

Please note that voltage losses could occur (due to cable length, cable 

section, voltage drop/sensor)! For longer cable lengths, the section of 

the connecting cables must be taken as large as possible.

Wiring examples for series-wiring, refer to appendix.

Protection is not required when pilot wires are laid. The cables however 

must be separated from the supply and energy cables. The max. fuse 

rate for a sensor chain depends on the section of the connecting cable 

of the sensor.

Cable design in case of serial diagnostics

The wiring capacitance of the connecting cable of the safety sensor 

must not exceed 50 nF.

Depending on the strand structure, normal unshielded 30 m long control 

cables LIYY 0.25 mm

2

 to 1.5 mm

2

 have a wiring capacitance of approx. 

3 … 7 nF.

When wiring SD devices, please observe the voltage drop 

on the cables and the current carrying capacity of the 

individual components.

Accessories for the series-wiring

For convenient wiring and series-wiring of SD components, 

the SD junction boxes PFB-SD-4M12-SD (variant for the 

field) and PDM-SD-4CC-SD (variant for control cabinet on 

carrier rail) are available along with additional comprehensive 

accessories. Detailed information is available on the Internet, 

www.schmersal.net.

Содержание CSS 34

Страница 1: ...he safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applicatio...

Страница 2: ...the position of movable safety guards In this application the safety sensor monitors the position of hinged sliding or removable safety guards by means of the coded electronic CST 34 or CST 180 actuat...

Страница 3: ...ISO 13849 1 IEC 61508 IEC 62061 PL e Control Category 4 PFH value 3 6 x 10 9 h SIL suitable for SIL 3 applications Mission time 20 years 3 Mounting 3 1 General mounting instructions Please observe the...

Страница 4: ...34 V 1 CSS 34 V CST 34 S 3 CSS 34 S CSS 34 V CST 34 S 3 CST 34 S 2 CSS 34 S CSS 34 V CST 34 S 2 CST 180 1 2 CSS 34 S CSS 34 V CST 180 1 2 3 4 Switch distance Actuators and switching distances to EN 60...

Страница 5: ...y channel must be observed Contactors with higher load currents must be controlled by intermediate control relays Information for the selection of suitable safety monitoring modules can be found in th...

Страница 6: ...he distance to the actuator increases and before the safety outputs are disabled thus stopping the machine IV Error warning sensor actuated On Flashes On 0 V 24 V After 30 minutes if the error is not...

Страница 7: ...e request byte changes from 1 to 0 or the safety guard is opened Faults at the safety outputs are only deleted upon the next release as the fault rectification cannot be detected sooner For devices wi...

Страница 8: ...2 3 5 4 6 8 X1 Y1 X2 7 Y2 7 Y2 SD IN SD OUT A1 A2 X1 Y1 X2 Y2 SD IN SD OUT Y1 Y2 SD IN 24 VDC GND CST 34 S 1 CSS 34 CST 34 S 1 CSS 34 Safety outputs Evaluation Gateway 6 Set up and maintenance 6 1 Fu...

Страница 9: ...PVC to IEC 60947 5 2 2007 A1 Ue 1 WH BN BN X1 Safety input 1 2 BN WH WH A2 GND 3 GN BU BU Y1 Safety output 1 4 YE BK BK OUT Diagnostic output SD output 5 GY GY GY X2 Safety input 2 6 PK VT PK Y2 Safe...

Страница 10: ...006 42 EC 2014 30 EU 2011 65 EU Machinery Directive EMC Directive RoHS Directive Applied standards EN 60947 5 3 2013 ISO 14119 2013 EN ISO 13849 1 2015 EN 61508 parts 1 7 2010 EN 62061 2005 AC 2010 A1...

Отзывы: