schmersal AZM 200 Скачать руководство пользователя страница 6

6

Operating instructions

Solenoid interlock

AZM 200

EN

System condition

Solenoid control

IN

LED

Safety outputs

Y1, Y2

Diagnostic outputs

OUT

Power to 
unlock

Power to 
lock

green red

yellow AZM 200 AZM 200 B -1P2P -1P2PW

Safety guard open

24 V (0 V)

0 V (24 V)

On

Off

Off

0 V

0 V

0 V

0 V

Door closed, 

actuator not inserted

24 V

0 V

On

Off

Off

0 V

0 V

0 V

0 V

Door closed, actuator inserted,  

not locked

24 V

0 V

On

Off

Fla-
shes

0 V

24 V

24 V

24 V

Door closed, actuator inserted,  

interlocking blocked

0 V

24 V

On

Off

Fla-
shes

0 V

24 V

24 V

0 V

Guard closed,  
actuator inserted and locked

0 V

24 V

On

Off

On

24 V

24 V

24 V

24 V

Error warning

1)

 

solenoid interlock locked 0 V

24 V

On

Flashes 

2)

On

24 V

1)

24 V

1)

0 V

0 V

Error

0 V (24 V)

24 V (0 V)

On

Flashes 

2)

Off

0 V

0 V

0 V

0 V

1) after 30 min: disabling due to fault

2) refer to flash code

Table 2: Error messages / flash codes red diagnostic LED

Flash codes 

(red)

Designation

Autonomous  

switch-off after

Error cause

1 flash pulse

Error (warning) at output Y1

30 min

Fault in output test or voltage at output Y1,  
although the output is disabled.

2 flash pulses

Error (warning) at output Y2

30 min

Fault in output test or voltage at output Y2,  
although the output is disabled.

3 flash pulses

Error (warning) cross-wire short

30 min

Cross-wire short between the output cables or fault at both outputs

4 flash pulses

Error (warning) temperature too high 30 min

The temperature measurement reveals an internal temperature  
that is too high

5 flash pulses

Actuator fault

0 min

incorrect or defective actuator

6 flash pulses

Error actuator combination

0 min

An invalid combination of actuators was detected  
(blocking bolt detection or tamper attempt).

Continuous  
red signal

Internal error

0 min

Device defective

6.3  Solenoid interlock with serial diagnostic function

Solenoid interlocks with serial diagnostic cable have a serial input and 

output cable instead of the conventional diagnostic output. If solenoid 

interlocks are wired in series, the diagnostic data is transmitted through 

the series-wiring of the inputs and outputs.

Max. 31 solenoid interlocks can be wired in series. For the evaluation of 

the serial diagnostics line either the PROFIBUS-Gateway SD-I-DP-V0-2 

or the Universal-Gateway SD-I-U-... are used.  This serial diagnostic 

interface is integrated as a slave in an existing field bus system.  In this 

way, the diagnostic signals can be evaluated by means of a PLC.

The response data and the diagnostic data are automatically and 

permanently written in an input byte of the PLC for each solenoid 

interlock in the series-wired chain. The request data for each solenoid 

interlock is transmitted to the component through an output byte of the 

PLC. In case of a communication error between the field bus gateway 

and the solenoid interlock, the switching condition of the solenoid 

interlock is maintained.

Error

A fault has occurred, which causes the safety outputs to be disabled. 

The fault is reset, when the cause is eliminated and bit 7 of the request 

byte changes from 1 to 0 or the safety guard is opened. Faults at the 

safety outputs are only deleted upon the next release, as the fault 

rectification cannot be detected sooner.

Automatic, electronic locking takes place if more than one 

fault is detected at the safety outputs or a cross circuit is 

detected between Y1 and Y2. This means that normal fault 

acknowledgement is no longer possible. To reset this type of 

interlocking, the solenoid interlock must be isolated from the 

power supply after elimination of the error causes.

Error warning

A fault has occurred, which causes the safety outputs to be disabled 

after 30 minutes. The safety outputs initially remain enabled. This 

enables the shutdown of the process in a controlled manner. An error 

warning is deleted when the cause of error is eliminated.

Diagnostic error (warning)

If an error (warning) is signalled in the response byte, detailed fault 

information can be read out.

Accessories for the series-wiring

To provide for a comfortable wiring and series-wiring of SD 

components, the connectors and the SD-2V-F-SK SD junction boxes 

(variant for the field in closed enclosure) and SD-2V-S-SK (variant for 

DIN rail mounting in the control cabinet) are available. 

When wiring SD devices, please observe the voltage drop on 

the cables and the current carrying capacity of the individual 

components.

Содержание AZM 200

Страница 1: ...e with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations an...

Страница 2: ...0 with non contact electronic safety sensors is designed for application in safety circuits and is used for monitoring the position of movable safety guards The safety function consists of safely switching off the safety outputs when the safety guard is unlocked or opened and maintaining the safe switched off condition of the safety outputs for as long as the safety guard is open For applications ...

Страница 3: ... 10 9 h PFD 2 2 x 10 4 SIL suitable for SIL 2 applications Service life 20 years The safety consideration of the guard locking function only applies for standard devices with monitored solenoid interlock AZM 200 1P2P W see Ordering code The actuation of the interlock must be compared with the external OSSD enabler If a shut down now occurs due to an unintentional unlocking this is detected by an e...

Страница 4: ...or is connected to electronic safety monitoring modules we recommend that you set a discrepancy time of 100 ms The safety inputs of the safety monitoring module must be able to blank a test impulse of approx 1 ms The safety monitoring module does not need to have a cross wire short monitoring function if necessary the cross wire short monitoring function must be disabled Information for the select...

Страница 5: ...or The safety outputs enable and allow a restart An interlocking chain must be permanently locked to enable the reactivation If more than one fault is detected at the safety outputs or a cross circuit is detected between Y1 and Y2 the solenoid interlock will be electronically locked and a normal fault reset will no longer be possible To reset this type of interlocking the solenoid interlock must b...

Страница 6: ...id interlocks can be wired in series For the evaluation of the serial diagnostics line either the PROFIBUS Gateway SD I DP V0 2 or the Universal Gateway SD I U are used This serial diagnostic interface is integrated as a slave in an existing field bus system In this way the diagnostic signals can be evaluated by means of a PLC The response data and the diagnostic data are automatically and permane...

Страница 7: ...it 1 7 Set up and maintenance 7 1 Functional testing The safety function of the safety components must be tested The following conditions must be previously checked and met 1 Fitting of the solenoid interlock and the actuator 2 Check the integrity of the cable entry and connections 3 Check the switch enclosure for damage 7 2 Maintenance We recommend a regular visual inspection and functional test ...

Страница 8: ...ge must be removed from all components up to the last component The voltage is supplied at both safety inputs of the terminal safety component of the chain considered from the safety monitoring module The safety outputs of the first safety component are wired to the safety monitoring module X1 Y1 X2 Y2 1 2 3 5 6 8 X1 X2 24V GND Y1 Y2 1 2 3 5 6 8 X1 4 Y1 4 Y1 X2 7 Y2 7 Y2 OUT 24V GND OUT SPS PLC IN...

Страница 9: ... IN Solenoid control SD input 8 4 RD OR without function 9 6 Connector plug ST1 M23 8 1 pole Connector plug ST2 M12 8 pole 1 2 9 3 4 5 6 7 8 5 8 4 3 2 1 7 6 Connecting cables with coupling female IP67 M23 8 1 pole 8 x 0 75 mm Connecting cables with coupling female IP67 IP69 M12 8 pole 8 x 0 23 mm to DIN 47100 Cable length Part number Cable length Part number 5 0 m 10 0 m 101209959 101209958 2 5 m ...

Страница 10: ...onform to the applicable European Directives Name of the component AZM 200 Type See ordering code Description of the component Interlocking device with electromagnetic inter lock for safety functions Relevant Directives Machinery Directive EMC Directive RoHS Directive 2006 42 EC 2014 30 EU 2011 65 EU Applied standards EN 60947 5 1 2004 AC 2005 A1 2009 EN 60947 5 3 2013 ISO 14119 2013 EN ISO 13849 ...

Отзывы: