AZM 200 AS

Operating instructions

Solenoid interlock

EN

6.2  Diagnostic information

Table 1: the diagnostic function of the AZM 200 AS solenoid interlock

System condition

Solenoid control (DO 0) LED

Condition

Power to 

unlock

Power to 

lock

green-red

3)

red

yellow

AS-i SaW-Code

(DI 0 ... DI 3)

Door open

1 (0)

0 (1)

green

Off

Off

static 0

Door closed, 
actuator not inserted

1 (0)

0 (1)

green

Off

Off

static 0

Door closed,  
actuator inserted  
(not locked)

1

0

green

Off

Flashes

AZM 200 ST-T-AS
AZM 200 B ST-T-AS
AZM 200 BZ ST-T-AS

static 0
dynamically
DI 0, DI 1: dynamic
DI 2, DI 3: static 0 

Door closed, actuator 
inserted and locked

0

1

green

Off

On

dynamically

Error warning

1)

,  

actuator inserted and locked. 
Shutdown approaching

0

1

green

flashes

2)

 

/ on

On

dynamically

Error

0 (1)

1 (0)

green

Flashes 

2)

Off

static 0

Internal error

0 (1)

1 (0)

green

On

Off

static 0

AS-i error: slave address = 0  
or communication error

1 (0)

0 (1)

red

depending 
on the 
condition

depending 
on the 
condition

static 0

1) after 30 min -> fault

2) refer to flash code

3) AS-i Duo-LED green/red

Table 2: Error messages / flash codes red LED

Flash codes (red)

Designation

Autonomous  

switch-off after

Error cause

4 flash pulses

Excess device temperature

max. 30 min

Internal excess temperature 

5 flash pulses

Actuator fault

0 min

incorrect or defective actuator

6 flash pulses

Error actuator combination

0 min

An invalid combination of actuators was detected 
(blocking bolt detection or tamper attempt)

Continuous red signal

Internal error

0 min

Device defective

5.5  Status signal "safety release"

The "safety release" status signal from a Safety at Work slave can be 

cyclically queried by the control system through the AS-i master. To that 

effect, the 4 input bits with the varying SaW code of a Safety at Work 

slave are evaluated through an OR operation with 4 inputs in the control 

system.

6.  Diagnostic

6.1  LED display

The solenoid interlock signals the operational state as well as errors 

through three coloured LED’s installed on the front side of the device.

The LED's have the following meaning (to EN 62026-2):

LED red/green
(AS-i duo LED):

 AS-Interface supply voltage / 
AS-Interface communication error 
or slave address = 0

Red LED:

Internal device error

Yellow LED:

Device status

40

220

155,5

5

6,5

32,5

7,5

20 1

±

50

15,5

M12

38

3,3

AS-i

Fault

Status

Error

Errors, which no longer guarantee the function of the AZM 200 AS 

solenoid interlock (internal error)s cause the safety outputs to be 

disabled within the risk time. Any error that does not immediately affect 

the safe functionality of the AZM 200 AS (e.g. the ambient temperature 

too high) will lead to a delayed shut-down (refer to table 2). After fault 

rectification, the error message can be reset by opening and closing 

the relevant guard door. The safety outputs of the safety monitor can be 

switched back on, thus enabling the machine.

Error warning

If a fault has occured, which still guarantees the function of the  

AZM 200 AS solenoid interlock, the system is safely switched off after 

30 minutes. The safety outputs of the safety monitor  initially remain 

enabled. The error message can be read out through the parameter 

port (refer to Table 1). Depending on the type of fault, the machine is 

not immediately shut down. The control system obtains a preliminary 

message, which can be used to shutdown the process in a controlled 

manner. An error warning is deleted/reset as soon as the error cause  

is eliminated.

Содержание AZM 200 AS

Страница 1: ...the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions...

Страница 2: ...is a safety switch with an interlock function for process protection The safety function consists of safely switching off the code transfer when the guard system is unlocked or opened and maintaining...

Страница 3: ...rin ciple of isolating the supply of power to the solenoid The safety classification for the release function only applies to devices with monitored interlock function in power to unlock version and w...

Страница 4: ...uts of the AS i safety monitor are enabled when the following conditions are met guard door detected the actuator is inserted AZM 200 BZ ST T AS The safety outputs of the AS i safety monitor are only...

Страница 5: ...cyclically queried by the control system through the AS i master To that effect the 4 input bits with the varying SaW code of a Safety at Work slave are evaluated through an OR operation with 4 inputs...

Страница 6: ...be observed refer to error warning switch off after 30 min 7 Set up and maintenance 7 1 Functional testing The safety function of the safety components must be tested The following conditions must be...

Страница 7: ...2013 Notified body for the prototype test T V Rheinland Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5122 01 15 Person authorised for the compilatio...

Страница 8: ...K A Schmersal GmbH Co KG M ddinghofe 30 42279 Wuppertal Germany Phone 49 202 6474 0 Telefax 49 202 6474 100 E Mail info schmersal com Internet www schmersal com...

Отзывы: