Operating instructions

Solenoid interlock

AZM 170 AS

EN

5.2  Magnet control

The control system with the AS-Interface Master can lock and unlock the 

solenoid interlock through the output bit 0 of the addressed AS-i slave 

AZM 170 AS. In the power to lock variant of the AZM 170 AS, the functio-

nal set of output bit 0 will cause the solenoid interlock to be locked. In the 

power to unlock variant of the AZM 170 AS, the functional set of output bit 

0 will cause the solenoid interlock to be unlocked.

5.3  Programming the slave address

The slave address is programmed through the M12 connector. Any 

address from 1 to 31 can be set by means of the AS-i bus master or a 

hand-held programming device.

5.4  Coniguration of the safety monitor

Depending on the component used, the AZM 170 AS can be conigured 

in the ASIMON coniguration software with the following safety monitors 

(also refer to the ASIMON manual). 

Dual-channel dependent with iltering

Suitable for: AZM 170 B ST-AS

The use of this safety monitor is especially advantageous on safety 

guards, which bounce or vibrate against the end stop during the closing 

operation.

•  Optionally with start-up test

•   Stabilisation time typically 0.5 up to 1.0 s

•   Synchronisation time typically 5.0 up to 10 s

The safety-monitoring module is only enabled after expiration of the 

stabilisation time and the synchronisation time must always be chosen 

so that it is considerably longer than the stabilisation time.

Dual-channel conditionally dependent

Suitable for: AZM 170 BZ ST-AS

•  Independent: In - 2

As long as the actuator remains inserted, the unlocked safety guard 

can be closed back at any time; at that moment, the safety outputs are 

reactivated. The safety guard must not be opened.

The redundancy and the "Safety guard closed" signal are not 

tested in this coniguration. To test these conditions, additio-

nal measures must be taken beyond the safety monitor .

Dual-channel dependent

Suitable for: AZM 170 B ST-AS

•   Synchronisation time typically: 1.0 s; 

for AZM 170 BZ ST-AS ininite (∞)

•   Optionally with start-up test

•   Optionally with local acknowledge

When the AZM 170 BZ ST-AS is used together with this safety-moni-

toring module for conducting the start-up test prior to every restart, the 

safety guard must be opened.

The coniguration of the safety monitor must be tested and 

conirmed by a qualiied and authorised safety expert/safety 

engineer. 

5.5  Status signal "safety release"

The "safety release" status signal from a Safety at Work slave can be 

cyclically queried by the control system through the AS-i master.  To 

that effect, the 4 input bits with the varying SaW code of a Safety at 

Work slave are evaluated through an OR operation with 4 inputs in the 

control system.

5.6  Read-out of the parameter port

The parameter port P0 to P3 of a solenoid interlock can be read out 

through the control interface of the AS-i master (see component de-

scription) by means of the "Write parameter" instruction (with hexadeci-

mal value F). This (non-safe) diagnostic information from the relected 

parameters or the answer to a "Write parameter instruction" can be 

used by the user for diagnostic purposes or for the control programme.

Parameter bit

Condition = 1

Condition = 0

0

Actuator inserted. 

The actuator can 

now be locked.

No actuator detected

1

Actuator inserted and 

locked

Actuator not locked

2

---

---

3

---

---