AZ 415-33ZPDK

Operating instructions

Safety switch

EN

3.3  Adjustment

In the unlocked condition, the safety guard is kept in a closed condition 

by the adjustable ball latch By rotating a hexagonal key wrench 

clockwise, the desired holding force can be increased; if the hexagonal 

key wrench is rotated counterclockwise, the holding force is decreased 

The holding force must always be set as low as possible

4.  Rear side Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition

Connection and sealing

For the cable entry, suitable cable glands with an appropriate degree 

of protection must be used Non-used openings must be sealed by 

means of threaded plugs The switching compartment must be cleaned 

(removal of cable excess etc); put back the cover after wiring and 

uniformly tighten the cover screws Minimum tightening torque for the 

cover screws: 1,2 Nm; bottom cover 0.7 + 0.1 Nm

The conductors of the connecting cables must not obstruct the 

movement of the switching lever.

4.2  Contact variants

Contacts are shown with safety guard closed

S2

S3

S1

21
23

31
33

22
24

32
34

13 11

14 12

Key

P

Actuated

Q

not actuated

A

positive break NC contact

5.  Set-up and maintenance

5.1  Functional testing

The safety function of the safety components must be tested  

The following conditions must be previously checked and met:

1 Fitting of the solenoid interlock and the actuator

2 Check the integrity of the cable entry and connections

3 Check the switch enclosure for damage

5.2  Maintenance

For use in extreme conditions, we recommend routine maintenance 

including the following steps:

1 Check for correct installation of the actuator and the switch

2 Remove particles of dust and soiling

3 Check cable entry and connections

Damaged or defective components must be replaced.

6.  Disassembly and disposal

6.1  Disassembly

The safety switchgear must be disassembled in a de-energised 

condition only

6.2  Disposal

The safety switchgear must be disposed of in an appropriate manner in 

accordance with the national prescriptions and legislations

Содержание AZ 415-33ZPDK

Страница 1: ...ed in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety...

Страница 2: ...perating principle By closing the safety guard switch insert S1 is released and switch insert S2 and S3 actuated differentiated operating principle When the actuator is fully inserted the safety guard is not subject to any ejection force 2 4 Technical data Standards IEC EN 60947 5 1 BG GS ET 15 Enclosure light alloy die cast enamel finish Protection class IP67 to IEC EN 60529 DIN VDE 0470 1 Contac...

Страница 3: ...m bottom cover 0 7 0 1 Nm The conductors of the connecting cables must not obstruct the movement of the switching lever 4 2 Contact variants Contacts are shown with safety guard closed S2 S3 S1 21 23 31 33 22 24 32 34 13 11 14 12 Key P Actuated Q not actuated A positive break NC contact 5 Set up and maintenance 5 1 Functional testing The safety function of the safety components must be tested The ...

Страница 4: ...rtal Germany Internet www schmersal com We hereby certify that the hereafter described components both in their basic design and construction conform to the applicable European Directives Name of the component AZ 415 Type See ordering code Description of the component Positive break position switch with separate actuator for safety functions Relevant Directives Machinery Directive RoHS Directive 2...

Отзывы: