Schmalz VS-V-D-PNP Скачать руководство пользователя страница 2

 

Vacuum switch 

 Pressure switch

 

VS-D 

Series

 

 

 

 

BA 30.30.01.00011_EN 
Status 03.2014 / Index 01 

2 / 3 

J. Schmalz GmbH, Aacher Straße 29, D-72293 Glatten 

Tel 07443/2403-0, Fax -259 

 

 

1x

 

 

 

 

 
 

Now the display switches to the adjustment of the upper margin. 
The 

display is alternating between “b-2“ and the preadjusted 

value. 

 

 

 

 
 

To adjust the upper margin, push ”Up”- or “Down”-key. 

 

 

 

 

 

 

Store the settings with the “Mode”-key. 

1x

 

 

 

 

 

 

8. Operating modes of the outputs

 

The outputs can be operated in two different modes. 
Each output can be adjusted independent of the other. 
The modes are described in the following. 

8.1 Hysteresis mode 

Settings are 

switching point 

and 

hysteresis h

Example: VS-V-D

 

H

 = -0.60 bar 

h

 = 0.15 bar 

N.O. (Normally Open) 

0 bar

h

off

on

off

H

-1 bar

 

At 0 bar, the digital output is off. 
When the vacuum level increases up to the 

switching point H

the digital output switches on. As long as the vacuum is higher 
than -0.45 bar ( = 0.6 bar - 0.15 bar), the digital output stays on. 
When the vacuum decreases and passes -0.45 bar, the digital 
output switches off. 
For the configuration of N.C. (Normally Closed), the output 
switches reverse ( off > H, on < H-h). 

Factory setting

: Output 1 & 2 in Hysteresis mode 

VS-V-D 

mmHg 

inHg 

kPa 

bar 

H - 1 

345 

13.6 

-46 

0.46 

h - 1 

50 

2.0 

-7 

0.07 

H - 2 

595 

23.4 

-79 

0.79 

h - 2 

50 

2.0 

-7 

0.07 

 

VS-P10-D 

psi 

kgf/cm² 

MPa 

bar 

– 1 

67 

4.75 

0.46 

4.6 

h - 1 

10 

0,70 

0.07 

0.7 

H - 2 

115 

8.2 

0.79 

7.9 

h - 2 

10 

0.7 

0.07 

0.7 

8.2 Window Comparator mode 

Settings are lower margin 

and upper margin 

b

Example: VS-V-D 
A

 = -0.45 bar 

b

 = -0.60 bar 

N.O. (Normally Open)

 

0 bar

A

off

w

on

on

on

b

-1 bar

off

off

 

At 0 bar, the digital output is off. 
When the vacuum level increases up to the 

lower

 

margin A

the digital output switches on. As long as the vacuum level is in 
the ”window” between the 

lower margin A

 and the 

upper 

margin b

, the digital output stays on. 

When the vacuum level becomes higher than the  

upper margin b

, the digital output switches off. 

For the configuration of N.C. (Normally Closed), the output 
switches reverse (A < off < b, A < on > b). 

Factory setting

: Output 1 & 2 in Window Comparator mode 

VS-V-D 

mmHg 

inHg 

kPa 

bar 

A - 1 

195 

7.6 

-26 

0.26 

b- 1 

400 

15.6 

-53 

0.53 

A - 2 

495 

19.4 

-66 

0.66 

b - 2 

645 

25.4 

-86 

0.86 

 

 

 

 

 

VS-P10-D 

psi 

kgf/cm² 

MPa 

bar 

A - 1 

38 

2.7 

0.26 

2.6 

b- 1 

77 

5.5 

0.53 

5.3 

A - 2 

96 

6.85 

0.66 

6.6 

b - 2 

125 

8.90 

0.86 

8.6 

9. Display of Peak and Bottom values 

The built-in memory stores in normal operation the peak value 
and bottom value since the switch was connected to the power 
supply.  
These will be displayed as follow: 
To display the peak valve, push the ”Up”-key 

1x

 

 

 

 

Peak value

 

 

 

 

 

To display the bottom valve, push the ”Down”-key 

1x

 

 

 

 

bottom value

 

 

 

 

10. Rotate display

 

If the mounting position is twisted (rotated on head), the display 
can be rotated . When connecting the power supply, push and 
hold the buttons “Up” and “Down”. 

Note that the decimal point lights up now at the upper 
margin of the display. The functions keys retain their 
function , that means that the “Up“-key shows downwards 
in twisted mounting position !

 

 

11. Locking the set values 

11.1 Standard versions

 

Whilst pushing the ”Mode“-key, push the ”Down“-key. The 
switch is locked, which means that the set values can’t be 
changed. On the display appears ”LoC”, the switch is locked. 

 

 

 

 

 

 

hold

 

 

 

When doing this once more, the switch gets unlocked and the 
settings can be changed again. 
On the display appears ”UnC”, the switch is unlocked. 

 

 

 

 

 

 

hold

 

 

 

11.2 Version with PIN code (VS-...-C)

 

The lock prevents unauthorised persons changing the settings. 
A 3-digit number combination (PIN code) guarantees that only 
people who know the PIN code (set by the operator) can change 
the settings. 

Activating the lock: 
To activate the lock

, press and hold the “Mode” button, then 

press the “Down” button. 

 

 

 

 

 

 

 

hold

 

 

 

Press the “Up” or “Down” button to change the right digit. 

 

 

 

 

 

 
 

The value for the right digit is saved when you press the “Mode” 
button. The centre digit flashes. 

1x

 

 

 

 

 

 
 

The centre digit can now be changed. 

Press the “Mode” button 

again to change the left digit. 
When the “Mode” button is pressed again, the PIN code entered 
is saved. “LoC” appears on the display and the lock is activated. 

1x

 

 

 

 

 
 

Deactivating the lock: 
To deactivate the lock, press and hold the “Mode” button, then 
press the “Down” button. 
“000” appears on the display and the right digit flashes. 

 

 

 

 

 

 

 

hold

 

 

 

The saved PIN code must be entered as described above for 
locking. If the PIN code is correct, “UnC” is displayed and the 
switch is unlocked. 

1x

 

 

 

 

 
 

If the PIN code is incorrect, “LoC” is displayed and the switch 
remains locked. 

1x

 

 

 

 

 
 

If you forget the PIN code saved, the switch can be 
unlocked in the SCHMALZ factory. 
 

12. Error messages

 

Error 

Message 

Solution 

 

 

Pressure during Zero-
point adjustment was 
higher than ±3% F.S. 

Make Zero-point 
adjustment again at 
environment pressure. 

 

Overcurrent at  
Output 1 

Loaded current 
exceeds rated power 

 

Overcurrent at  
Output 2 

of 180mA max. 
Check output. 

 

 

*

 

Applied pressure 
exceeds measuring 
range. 

Apply pressure within 
the measuring range. 

 

EEPROM defective, 
calibration storage 
could not be read 
anymore 

Switch defective, 
replace it 

*  A display change from 0.00 to 

–FF or e.g. 0.01 at a

 

tmospheric pressure is not an error, but caused by 

 

fluctuations in the air pressure. 

 

This can be rectified by setting the zero point. 

 

The zero point must also be set after performing a “Clear 

 

all” (CLA). 